BACnetWriteFileObjectContents (FUN)ΒΆ
FUNCTION BACnetWriteFileObjectContents : IEC_BACNET_STATUS
Function initiates a file data transfer to write the file object data.
This function will start a file data transfer to write the specified file object data in the specified device. In case of stream data in the specified file object the data is expected in binary format. In case of record data in the file object the record is expected also in binary format but is may be expected in the extended format for each record by a record marker and record size. If the records data is not in the expected format some error will be returned.
Return: IEC_BACNET_STATUS
- InOut:
Scope
Name
Type
Comment
Return
BACnetWriteFileObjectContentsInput
pInfoPOINTER TO IEC_BACNET_FILEACCESS_INFO
Pointer to information which specifies which device and which file object will be accessed and the format of the file data in case of a record access file object.
pICallbackCmpEventMgr.ICmpEventCallbackPointer to the event-callback interface. Event-callback argument type is EVT_BACNET_FILEACCESS_PROGRESS. Purpose documented in BACstack: Pointer to the user application callback funktion to inform about failures and progress information during the data transfer procedure.
pAPDUParamsPOINTER TO IEC_BACNET_APDU_PROPERTIES
A pointer to the structure which contains a set of APDU properties to control the timing and size of transmitted frames for this request. It temporarily overwrites the global APDU settings made in the source device from which this request is sent and which parameters would control this request if this pointer is NULL.
pTransactionTokenPOINTER TO BACnetAsyncTransactionToken
Transaction token of the asynchronous call - see BACnetAsyncTransactionToken.