Programming a Trend Visualization
To display a trend recording in the visualization, you define which application provides which trend recording. You define the display by means of the Properties of the trend element and the controls used.
Defining the application and data source
The visualization task and the trend recording task generally run under the same application. If this is not the case, then the application containing the visualization task requires a data source manager.
Select a trend element in the active visualization editor.
The properties of the trend element are displayed.
Double-click the in the .
Use the Input Assistant (
) to select the application. You can also specify the name of the application directly.
Defining the trend recording to visualize
Select a trend element in the active visualization editor.
The properties of the trend element are displayed.
Click in the value field of .
Select trend recording is displayed. The trend recordings available application-wide are listed under Available trend recordings.
Select a trend record below Available trend recordings.
Click
.The trend recording is located under Selected trend recording.
Click OK to confirm the entry.
The selected trend recording is listed in Values in .
Adding a control
Select a trend element in the active visualization editor.
Click .
The Trend Wizard dialog opens.
Select the desired control. Examples: Date Range Picker, Time range Range Picker, Legend. Click OK to confirm.
The selected controls are inserted for the trend element. You can move them to any position you like. In the Properties of the trend element, the controls are shown below Assigned controls.
Removing a control
Tip
A control that was added with the help of the Trend Wizard cannot be deleted via the Trend wizard dialog.
Select a control of a trend in the active visualization editor.
Press Del or Delete to delete the element.
Select the trend in the active visualization editor.
Delete the assigned value in .
Important
It is absolutely necessary to delete this reference manually. The property is not deleted automatically by deleting the control.
Configuring the coordinate system of the trend diagram
Select a trend in the active visualization editor.
Use the command.
The Display Settings dialog opens.
Adapt the settings as needed.
Reading a trend value at runtime
Open .
Select a trend element in your visualization.
The properties of the trend element are displayed.
Select the and options.
A cursor is drawn in the coordinate system.
Select the option.
Download the application to the controller and start the application.
Tip
If the diagram "runs”, then the date range has been placed in such a way that its end time is the current time.
Select the date range so that the diagram does not run. If necessary, drag the scroll bar to an earlier date range.
A cursor is available. The tooltip of the cursor informs you of the trend values. For each trend variable, the legend displays the value at the point in time at which the cursor is positioned.
Deleting the trend recording history
You can insert an input element in the visualization which the operator can use to delete the previous value recording in the trend visualization at runtime. The curve displayed until then is removed and the display starts over.
In the application (example: in the program
PLC_PRG), implement the following code:itfTrendStorageWriter : ITrendStorageWriter; itfTrendStorageWriter3 : ITrendStorageWriter3; sTrendRecordingName : STRING := 'TrendRecording'; itfTrendRecording := GlobalInstances.g_TrendRecordingManager.FindTrendRecording(ADR(sTrendRecordingName)); xClearHistoryTrend: BOOL; IF xClearHistoryTrend THEN itfTrendRecording := GlobalInstances.g_TrendRecordingManager.FindTrendRecording(ADR(sTrendRecordingName)); IF itfTrendRecording <> 0 THEN itfTrendStorageWriter := itfTrendRecording.GetTrendStorageWriter(); IF __QUERYINTERFACE(itfTrendStorageWriter, itfTrendStorageWriter3) THEN itfTrendStorageWriter3.ClearHistory(); END_IF END_IF END_IFIn the visualization of the trend recording, add a button for deleting the previous curve. Configure its Toggle property with the variable
PLC_PRG.xClearHistoryTrend.When
xClearHistoryTrendis set toTRUE, the previously recorded curve is deleted. The recording immediately starts again.