Tab: Redundancy Settings – General
The tab includes the configuration of the watchdog, the task with the desired services, and the fieldbus for redundancy.
Redundancy task name | Name of the task that is synchronized between both devices Only this one task is synchronized. Example: NoteThe task name is also entered in the RTS configuration file when you click the Write button. Alternatively, you could also manually edit the file. |
Timeout (ms) | Time span to wait for the response from the active PLC After that, the standby PLC switches to standalone mode. In this case, the task execution is delayed by this time span. Example: Recommendation: Set the value higher than the maximum task jitter time plus the maximum transmission time for redundancy messages. NoteThe setting is also stored in the RTS configuration file ( NoteWhen you deploy the CIFX-DP adapter, set the timeout to 100 ms in order to remain in sync in case of a reset. |
Synchronization timeout (ms) | Time span to wait during a synchronization. After this period of time, the standby PLC switches to standalone mode. You can set the value optimally if you first determine the required synchronization time after getting a system trace from the PLC. See the Record the needed sync time in system trace option below. Example: If the synchronization takes longer than the timeout is allowed in Timeout (ms), and the jitter of PLC 1 is acceptable, then you can use this setting. Then the time span until the response has to be received is extended by this value. TipIncrease this setting in step-by-step when you encounter these kinds of synchronization problems. The logger message Synchronization terminated after x ms because of SyncWaitTime refers to this situation. NoteA redundant system switches to the synchronization phase for the start of the redundant PLC, a download, an online change, and the synchronization by means of user commands. During the synchronization phase, the task cycle time of the active PLC can be longer. |
Setting the TipWhen you click the Write button, the values set here in the development system are transferred to the runtime system. | |
Auto sync |
|
Data sync always |
|
Debug messages |
|
Record the needed sync time in system trace |
This option, which can be enabled here in the dialog, is entered in |
EtherCAT |
NoteThe NIC settings for the adapter have to be set on both PLCs. You need to verify this. You can use the Browse button to automatically search for the respective PLC. |
Profibus |
|
Read | Reads into the dialog the current settings of the redundancy link for PLC 1 |
Write | Transfers the available settings of the redundancy link on both devices |