Skip to main content

Operators

CODESYS V3 supports all IEC 61131-3 operators. These operators are recognized implicitly throughout the project. In addition to these IEC operators, CODESYS also supports some non-IEC 61131-3 operators.

Operators are used in blocks, such as functions.

Tip

For information about the processing order (binding strength) of the ST operators, see the "ST expressions" chapter.

Caution

For operations with floating-point data types, the computational result depends on the applied target system hardware.

Caution

For operations with overflow or underflow in the data type, the computational result depends on the applied target system hardware.

Overflow/underflow in the data type

The CODESYS compiler generates code for the target device and computes temporary results always with the native size that is defined by the target device. For example, computation is performed at least with 32-bit temporary values on x86 and ARM systems and always with 64-bit temporary values on x64 systems. This provides considerable advantages in the computation speed and often also produces the desired result. But this also means that an overflow or underflow in the data type is not truncated in some cases.

Example 106. Examples

Example 1

The result of this addition is not truncated and the result in dwVar is 65536.

VAR
wVar : WORD;
dwVar: DWORD;
END_VAR

wVar := 65535;
dwVar := wVar + 1;

Example 2

The overflow and underflow in the data type is not truncated and the results (bVar1, bVar2) of both comparisons are FALSE on 32-bit and 64-bit hardware.

VAR
wVar1 : WORD;
wVar2 : WORD;
bVar1 : BOOL;
bVar2 : BOOL;
END_VAR

wVar1 := 65535;
wVar2 := 0;
bVar1 := (wVar1 + 1) = wVar2;
bVar2 := (wVar2 - 1) = wVar1;

Example 3

By the assignment to wVar3, the value is truncated to the target data type WORD and the result bvar1 is TRUE.

VAR
wVar1 : WORD;
wVar2 : WORD;
wVar3 : WORD;
bVar1 : BOOL;
END_VAR

wVar1 := 65535;
wVar2 := 0;
wVar3 := (wVar1 + 1);
bVar1 := wVar3 = wVar2;

Example 4

In order to force the compiler to truncate the temporary results, a conversion can be inserted.

The type conversion makes sure that both comparisons are 16-bit only and the results (bVar1, bVar2) of both comparisons are each TRUE.

VAR
wVar1 : WORD;
wVar2 : WORD;
bVar1 : BOOL;
bVar2 : BOOL;
END_VAR

wVar1 := 65535;
wVar2 := 0;
bVar1 := TO_WORD(wVar1 + 1) = wVar2;
bVar2 := TO_WORD(wVar2 - 1) = wVar1;


Arithmetic operators

ADD

SUB

MUL

DIV

MOD

MOVE

INDEXOF

SIZEOF

XSIZEOF

Bitstring operators

AND

OR

XOR

NOT

AND_THEN

OR_ELSE

Bitshift operators

SHL

SHR

ROL

ROR

Selection Operators

SEL

MAX

MIN

LIMIT

MUX

Comparison Operators

A comparison operator is a Boolean that compares two inputs (first and second operand).

GT

LT

LE

GE

EQ

NE

Address operators

ADR

Content Operator

BITADR

Call operators

CAL

Type conversion operators

You can explicitly call type conversion operators. The type conversion operators described below are available for typed conversions from one elementary type to another elementary type, as well as for overloading. Conversions from a "larger" type to a "smaller" type are also implicitly possible (for example, from INT to BYTE or from DINT to WORD).

Typed conversion: <elementary data type> _TO_ another elementary data type>

Overloaded conversion: TO_ <elementary data type>

Elementary Data Types

<elementary  data type> =
__UXINT | __XINT | __XWORD | BIT | BOOL | BYTE | DATE | DATE_AND_TIME | DINT | DT | DWORD | INT | LDATE | LDATE_AND_TIME | LDT | LINT | LREAL | LTIME | LTOD | LWORD | REAL | SINT | TIME | TOD | UDINT | UINT | ULINT | USINT | WORD

The keywords T, TIME_OF_DAY and DATE_AND_TIME are alternative forms for the data types TIME, TOD, and DT. T, TIME_OF_DAY and DATE_AND_TIME are not represented as a type conversion command.

Important

If the operand value for a type conversion operator is outside of the value range of the target data type, then the result output depends on the processor type and is therefore undefined. This is the case, for example, when a negative operand value is converted from LREAL to the target data type UINT.

Information can be lost when converting from larger data types to smaller data types.

String manipulation when converting to STRING or WSTRING

When converting the type to STRING or WSTRING, the typed value is left-aligned as a string and truncated if it is too long. Therefore, declare the return variable for the type conversion operators <>_TO_STRING and <>_TO_WSTRING long enough that the string has enough space without any manipulation.

REAL, LREAL

TIME, LTIME

DATE, DT, TOD, LDATE, LDT, LTOD

STRING, WSTRING

TRUNC

TRUNC_INT

Numeric Operators

ABS

SQRT

LN

LOG

EXP

EXPT

SIN

ASIN

COS

ACOS

TAN

ATAN

Namespace operators

Namespace operators are extended from IEC 61131-3 operators. They make it possible for you to provided unique access to variables and modules, even when you use the same name multiple times for variables or modules in a project.

Global Namespace

Namespace for Global Variable Lists

Enumeration Namespace

Library Namespace

__POOL

Multicore operators

Working with different tasks requires the synchronization of these tasks. This is especially true when working on multicore platforms. CODESYS provides some special operators to support this synchronization.

These operators are extensions of IEC-61131-3. The operators TEST_AND_SET and __COMPARE_AND_SWAP are used for similar tasks.

TEST_AND_SET

__COMPARE_AND_SWAP

__XADD

Other operators

__DELETE

__ISVALIDREF

__NEW

__QUERYINTERFACE

__QUERYPOINTER

INI

__TRY, __CATCH, __FINALLY, __ENDTRY

__POSITION

__POUNAME