Object: Property

Symbol: _cds_icon_interface_property.png

Keyword: PROPERTY

Properties are an extension of the IEC 61131-3 standard and a tool for object-oriented programming.

Properties are used for data encapsulation because they allow for external access to data and act as filters at the same time. For this purpose, a property provides the accessor methods Get and Set which allows for read and write access to the data of the instance below the property.

You can add a property with accessor methods below a program, a function block, or a global variable list. Click Project → Add Object → Property to open the Add Property dialog.

Tip

You can add an interface property below an interface.

When you copy a property that is inserted below a POU and add it below an interface, or if you move the property there, the included implementations are removed automatically.

Dialog: Add Property

Function: Creates a new property below the selected POU when the dialog is closed.

Call: Project → Add Object → Property; context menu

Requirement: A program (PRG), a function block (FUNCTION_BLOCK), or a global variable list (GVL) is selected in the POUs view or the Devices view.

Name

Name (identifier) of the property

Example: prop_iA

Return type

Default type or structured type of return value

Example: INT

Implementation language

Example: Structured Text (ST)

Access specifier

Controls access to data

PUBLIC or unspecified

Access is not restricted.

PRIVATE

Access is restricted to the program, function block, or GVL.

The object is marked as (private) in the POU or device view. The declaration contains the keyword PRIVATE.

PROTECTED

Access is restricted to the program, function block, or GVL with its derivations.

The object is marked as (protected) in the POU or device view. The declaration contains the keyword PROTECTED.

INTERNAL

Access is restricted to the namespace (library).

The object is marked as (internal) in the POU or device view. The declaration contains the keyword INTERNAL.

Abstract

standard icon: Identifies that the property does not have an implementation and the implementation is provided by the derived FB

Add

Adds a new property be low the selected object and below that the accessor methods Get and Set

Note: When you select a property, you can also add a previously removed accessor explicitly by clicking Add Object.

Editor: Property

You can program the data access in the editor. The code can contain additional local variables. However, it must not contain any additional input variables or (as opposed to a function or method) output variables.

Example 535. Example
_cds_img_property.png

Function block FB_A

FUNCTION_BLOCK FB_A
VAR_INPUT
END_VAR
VAR_OUTPUT
END_VAR
VAR
    iA : INT;
END_VAR

iA := iA + 1;

Property prop_iA

PROPERTY PUBLIC prop_iA : INT

Accessor method FB_A.prop_iA.Get

prop_iA := iA;

Accessor method FB_A.prop_iA.Set

iA := prop_iA;
PROGRAM PLC_PRG
VAR
        fbA : FB_A;
        iVar: INT;
END_VAR

fbA();
IF fbA.prop_iA > 500 THEN
        fbA.prop_iA := 0;
END_IF
iVar := fbA.prop_iA;


Get and Set accessors

The call of the Set accessor is written to the property. Then it is used in the same way as an input parameter. When the Get accessor is called, the property is read. It is used in the same way as an output parameter. Access is restricted in each case by means of access modifiers (qualifiers). As a result, the objects are identified accordingly.

When a property is accessed as read only or write only, you can delete the unneeded accessors.

You can add accessors explicitly by selecting a property and clicking Add Object. A dialog opens, either Add Get accessor or Add Set accessor. There you can set the implementation language and the access.

Table 62. Dialog: Add Get (Set) Accessor

Implementation language

Example: Structured Text (ST)

Access specifier

Qualifier for the declaration part

PUBLIC or unspecified

Access is not restricted.

PRIVATE

Access is restricted to the program, function block, or GVL.

The object is marked as (private) in the POU or device view. The declaration contains the keyword.

PROTECTED

Access to the property is restricted to the program, function block, or GVL and its derivations. The declaration contains the keyword.

The object is marked as (protected) in the POU or device view.

INTERNAL

Access to the method is restricted to the namespace (the library).

The object is marked as (internal) in the POU or device view. The declaration contains the keyword.

Add

Adds the accessor methods Get or Set below the selected property.



Monitoring of properties in online mode

The following pragmas are provided for the monitoring of properties in online mode. You insert them at the top position of the property definition:

  • {attribute 'monitoring' := 'variable'}

    Each time the property is accessed, CODESYS saves the actual value to a variable and displays the value of this variable. This value can become outdated if no more access to the property takes place in the code.

  • {attribute 'monitoring' := 'call'}

    Each time the value is displayed, CODESYS calls the code of the Get accessor. If this code contains a side effect, then the monitoring executes the side effect.

. You can monitor a property with the help of the following functions.
  • Inline monitoring

    Requirement: The Enable inline monitoring option is selected in the Text Editor category of the Options dialog.

  • Watch List

Input support when generating inheriting POUs

When you doing object-oriented programming and using the inheritance (EXTENDS keyword) of POUs, you can get support as follows:

When you insert an action, a property, a method, or a transition below a POU derived from a base POU, the Add … dialog opens. Then the input field for the name extends to a list box. The list box contains a valid selection from the actions, properties, methods, or transitions available in the base POU. Now you can, for example, easily accept a method of the base POU and then adapt it to the derived function of the POU.

Methods and properties with the access specifier PRIVATE are not listed here because they are also not inherited. Methods and properties with the access specifier PUBLIC automatically get a blank access specifier field when accepting into the derived POU, which means the same thing functionally.

For more information, see the following: Property, Method, Transition, and Action

Example 536. Example