Command: Connect Edge Gateway
Symbol: 
Function: The command opens the Connect or Reconfigure Edge Gateways view for configuring the Edge Gateway. Via the Edge Gateway, the PLC network is connected to the CODESYS Automation Server.
Call: CODESYS menu:
Requirement:
- The CODESYS Automation Server Connector package is installed. 
- The gateway of the current PLC is running. 
View: Connect or Reconfigure Edge Gateways
| Gateway hostname / IP | List box with all currently available Edge Gateways The selected gateway has to be reachable via the network. When you select a gateway here, the Gateway port field is updated automatically. As an alternative to the previous step, you could also manually specify Gateway hostname / IP and Gateway port. | 
| Gateway port | Port of the selected gateway | 
| Check / Refresh Gateway Information | Button to check and refresh the displayed information for the gateway | 
| Configuration mode | Shows whether or not the configuration mode is enabled. 
 Note: When you use the Allow Edge Gateway Configuration  command to enable the configuration, you also have click the Check / Refresh Gateway Information button to refresh the view. The Allow Edge Gateway Configuration command is available when you click the gateway symbol  | 
| Proxy URL | URL of the proxy server | 
| Proxy user | User name for the proxy server | 
| Proxy password | Password for the proxy server | 
| Save proxy settings | The Proxy URL, Proxy user, and Proxy password settings are saved. | 
| Delete proxy settings | Any current proxy settings that exist on the Edge Gateway are deleted. | 
| Edge communication | Displays whether or not communication is enabled via the Edge Gateway: 
 | 
| Configured URL | URL of the CODESYS Automation Server for which the Edge Gateway is configured | 
| Certificate state | Displays whether or not and for how long the certificate is valid | 
| Temporarily Disable Edge Communication | Requirement: Configuration mode is enabled and Edge communication is enabled. Disables the communication with the Automation Server via the Edge Gateway until you click the Enable Edge Communication button to enable it again. | 
| Enable Edge Communication | Requirement: Configuration mode is enabled and Edge communication is disabled temporarily. Enables the communication to the Automation Server via the CODESYS Automation Server. | 
| Disconnect Edge | Ends the communication with the Edge Gateway and deletes the configuration of the Edge Gateway Note: This command does not delete the Edge Gateway configuration on the CODESYS Automation Server. When you select the corresponding Edge Gateway in this view in the CODESYS Automation Server in Known Edge Gateways on server group and then click the Show Edge Gateway on Server button, the  view open on the CODESYS Automation Server. There you can click the  | 
| The following information about the certificate is displayed only when the Show details option is selected. | |
| Certificate thumbprint | Displayed when the Edge Gateway is connected with the Automation Server | 
| Name | Name of the Edge Gateway | 
| Vendor | Vendor of the Edge Gateway | 
| Version information | Version of the Edge Gateway | 
| Node name | Displayed when the Edge Gateway is connected with the CODESYS Automation Server | 
| Target ID / Type | Displayed when the Edge Gateway is connected with the CODESYS Automation Server | 
| Server URL | URL of the CODESYS Automation Server | 
| Check / Refresh | Requirement: The URL of a CODESYS Automation Server is specified in Server URL. Button to check and refresh the displayed information Opens the Automation Server – Sign In dialog. When you click OK to acknowledge the dialog successfully, the Edge Gateway of the Automation Server are displayed in Known Edge Gateways on server. | 
| Name on server | Requirement: The configuration mode is enabled and the Edge Gateway is not connected yet. If you specify a new name here and then click Connect to Server, then a new gateway is created with this name on the Automation Server. | 
| Description | This description is displayed with the gateway on the CODESYS Automation Server. | 
| Connect to Server | Requirement: The configuration mode is enabled. If a new name has been specified for Name on server, then the configured Edge Gateway with this new name is created on the Automation Server. The recently created gateway is displayed on the CODESYS Automation Server in . The root certificate of the server is transferred to the Certificate Store as a trustworthy certificate. The corresponding certificate is generated there and the thumbprint is transferred to the CODESYS Automation Server. The information of the Certificate state field in this view in the Edge Gateway and CODESYS Automation Server groups is refreshed and shows that the certificate is valid. The Certificate thumbprint is identical in both groups. | 
| Known Edge Gateways on server | Display the gateways that are registered on this Automation Server | 
| Certificate state | Displays whether or not and for how long the certificate is valid | 
| Certificate thumbprint | Requirement: The Show details option is selected. Displayed when the Edge Gateway is connected with the Automation Server | 
| Show Edge Gateway on Server | Opens the Automation Server displayed in Server URL with the . The Edge Gateway selected in Known Edge Gateways on server is also displayed there. | 
| Network Scan on Server | Opens the Automation Server shown in Server URL with the view. The Edge Gateway selected in Known Edge Gateways on server is displayed, and a network scan is started automatically. | 
| Replace Existing Edge Gateway | Requirement: The configuration mode is enabled. Replaces the Edge Gateway selected in Known Edge Gateways on server on the Automation Server with the Edge Gateway configured in the Edge Gateway group. If you are not signed in to the Automation Server yet, then the Automation Server – Sign In dialog opens first. | 
| Renew Certificate | Requirement: The configured Edge Gateway is connected to the Automation Server and the configuration mode is enabled. The certificate is renewed on the Edge Gateway and on the Automation Server. The Certificate state and Certificate thumbprint fields are refreshed in the same Connect or Reconfigure Edge Gateways view. The new certificate is valid for 6 months. | 
| Reconnect (Repair Configuration) | Requirement: The configuration mode is enabled. An error in the certificate is repaired. For example, if the thumbprint of the certificate was generated incorrectly, then this command corrects the error. | 
| Show details | The detailed information Certificate thumbprint, Vendor, Version info, Node name, and Target ID / Type is displayed. | 



