RemoteProcedureCalls (GVL)ΒΆ
List of available RPCs of the CLServer FB. All results are returned in Intel Byte Order (= little Endian)
- Attributes:
- qualified_only
- InOut:
- Scope - Name - Type - Initial - Comment - Constant - CODESYS_OBJECT_UUID - STRUCT(Data1 := 16#25CE9503, Data2 := 16#674, Data3 := 16#47EE, Data4 := [16#86, 16#20, 16#77, 16#3C, 16#1B, 16#93, 16#D0, 16#E1]) - UUID of CODESYS - SYSTARGET_INTERFACE_UUID - STRUCT(Data1 := 16#27E2FD4E, Data2 := 16#4ED8, Data3 := 16#41EA, Data4 := [16#B2, 16#95, 16#6, 16#C1, 16#7F, 16#27, 16#3B, 16#96]) - UUID of SysTarget library - END_POINT_MAPPER_INTERFACE_UUID - STRUCT(Data1 := 16#E1AF8308, Data2 := 16#5D1F, Data3 := 16#11C9, Data4 := [16#91, 16#A4, 16#8, 16#0, 16#2B, 16#14, 16#A0, 16#FA]) - UUID of End Point Mapper - NDR_32_BIT_UUID - STRUCT(Data1 := 16#8A885D04, Data2 := 16#1CEB, Data3 := 16#11C9, Data4 := [16#9F, 16#E8, 16#8, 16#0, 16#2B, 16#10, 16#48, 16#60]) - UUID of 32 bit NDR - GetTargetNodeName - STRUCT(ObjectID := CODESYS_OBJECT_UUID, InterfaceID := SYSTARGET_INTERFACE_UUID, OperationNumber := SysTargetOperationNumber.GetTargetNodeName) - Get a human readable name that identifies this node in the network. NOTE: This could be the registered host name of the target in the network.
- Parameter value: none 
- Return value: WSTRING(64) Type is 2 byte unicode! 
 
 - GetTargetVersion - STRUCT(ObjectID := CODESYS_OBJECT_UUID, InterfaceID := SYSTARGET_INTERFACE_UUID, OperationNumber := SysTargetOperationNumber.GetTargetVersion) - Returns the target version.
- Parameter value: none 
- Return value: DWORD 
 
 - GetTargetId - STRUCT(ObjectID := CODESYS_OBJECT_UUID, InterfaceID := SYSTARGET_INTERFACE_UUID, OperationNumber := SysTargetOperationNumber.GetTargetId) - Returns the TargetId. NOTE: Highword of the TargetId is the VendorId! The VendorId is managed by 3S.
- Parameter value: none 
- Return value: DWORD