FBS_ANTI (ENUM)ΒΆ

TYPE FBS_ANTI :

Definition of SF_Antivalent function block states and its diagnostic values.

Attributes:
qualified_only
InOut:

Name

Initial

Comment

IDLE

16#0

The function block is not active (initial state).

INIT

16#8801

An activation has been detected by the FB and the FB is now activated.

OUT_ENABLED

16#8000

The inputs switched to the Active state in antivalent mode.

WAIT_FOR_NO

16#8802

ChannelNC has been switched to TRUE - waiting for ChannelNO to be switched to FALSE; discrepancy timer started.

WAIT_FOR_NC

16#8804

ChannelNO has been switched to FALSE - waiting for ChannelNC to be switched to TRUE; discrepancy timer started.

FROM_ACTIVE_WAIT

16#8806

One channel has been switched to inactive; waiting for the second channel to be switched to inactive too; discrepancy timer started.

ERROR_1

16#C010

Discrepancy time elapsed in state WAIT_FOR_NO (16#8802).

ERROR_2

16#C020

Discrepancy time elapsed in state WAIT_FOR_NC (16#8804).

ERROR_3

16#C030

Discrepancy time elapsed in state FROM_ACTIVE_WAIT (16#8806).