Apply_Attributes (FB)¶
FUNCTION_BLOCK Apply_Attributes EXTENDS BaseService
This function block is used for calling the “Apply_Attributes” service of a specific instance of a CIP object. As a result, the attributes that were previously set with “Get_Attribut_Single” or “Get_Attribut_All” are adopted and saved by the adapter.
- InOut:
Scope
Name
Type
Comment
Inherited from
Input
xExecute
BOOL
Rising edge: Action startsFalling edge: Resets outputsIf a falling edge occurs before the function block has completed its action, the outputs operate in the usual manner and are only reset if either the action is completed or in the event of an error. In this case, the corresponding output values (xDone
,xError
) are present at the outputs for exactly one cycle.ETrig
Output
xDone
BOOL
TRUE
: Action successfully completedETrig
xBusy
BOOL
TRUE
: Function block activeETrig
xError
BOOL
TRUE
: Error occurred, function block aborts actionFALSE
: No errorETrig
Input
itfEtherNetIPDevice
IEtherNetIPService
BaseService
eClass
BaseService
dwInstance
DWORD
BaseService
Output
eError
BaseService