ETC_FoE_Upload (FB)ΒΆ
FUNCTION_BLOCK ETC_FoE_Upload
Function block to upload a file from the EtherCAT Slave.
- InOut:
- Scope - Name - Type - Initial - Comment - Input - xExecute- BOOL- Rising edge: ACTION starts Falling edge: Resets outputs If a falling edge occurs before the function block has completed its action, the outputs operate in the usual manner and are only reset if either the action is completed or in the event of an error. In this case, the corresponding output values (xDone, xError) are present at the outputs for exactly one cycle. - usiCom- USINT- 1 - Index of master 1: first ETC master - uiDevice- UINT- The physical slave address to access the EtherCAT slave - usiChannel- USINT- 1 - not used in the moment because channel is set automatically - pbyData- POINTER TO BYTE - pointer to buffer to read - udiDataSize- UDINT- Size of buffer - dwPassword- DWORD- Password for file to read - strFilename- STRING- Filenname to read fromthe EtherCAT slave - Output - xDone- BOOL- TRUE: Action successfully completed - xBusy- BOOL- TRUE: Function block active - xError- BOOL- TRUE: Error occurred, function block aborts action, FALSE: No error - Errorcode- if xError is true, then this output shows the error reason - strErrorText- STRING- Error code as an string - udiDataRead- UDINT- Number of Bytes that could be read 
