TraceMgrRecordUpdate4 (FUN)¶
FUNCTION TraceMgrRecordUpdate4 : RTS_IEC_RESULT
Stores multiple values with seperate timestamps in the ring buffer of a trace record.
This function can be used to provide the data for so called system parameters from the IEC application. (See TRACE_VAR_ADDRESS_FLAGS_SYSTEM.)
Note
in contrast to TraceMgrRecordUpdate2, the timestamp of the values and the values itself are provided in seperate lists by the caller.
Note
the number of timestamps must be the same as the number of data values. ulEntries must match to this number.
- InOut:
Scope
Name
Type
Comment
Return
TraceMgrRecordUpdate4RTS_IEC_RESULT- Returns the runtime system error code (see CmpErrors.library):
ERR_PARAMETER if hPacket or hPrevRecord is not a valid handle
ERR_NOTINITIALIZED if the packet is not currently recording (not started, trigger reached, …)
ERR_PENDING if no value is recorded for this cycle due to TracePacketConfiguration.ulEveryNCycles
Input
hPacketRTS_IEC_HANDLEThe trace packet handle
hRecordRTS_IEC_HANDLEThe trace record handle
pTimestampsPOINTER TO UDINT
The address of the first timestamp of the variable values
pDataValuesPOINTER TO BYTE
The address of the first variable value of the list to copy
ulEntriesUDINTThe number of variables to be updated