IEC_BACNET_ACK_ALARM_INFO (STRUCT)¶
TYPE IEC_BACNET_ACK_ALARM_INFO : STRUCT
This is the main structure for sending Acknowledge Alarm service request.
- InOut:
Name
Type
Comment
processIDThe handle of a process within the recipient device that has received the event notification.
eventObjectIDThis contains the identifier of the origin object of the event notification.
eventStateThis contains the value of the ‘To State’ from the event notification that is acknowledged.
timeStampThis contains the same ‘Time Stamp’ that was received in the event notification that is acknowledged.
ackSourceThis contains the identification of the human operator or process that has initiated this acknowledge.
ackTimeThis contains the time at which an operator or process acknowledged the event notification.