BACnetChangeListErrorCbCompletion (FUN)¶
FUNCTION BACnetChangeListErrorCbCompletion : IEC_BACNET_STATUS
Sends a ChangeList error.
Completes an Add-List-Element or Remove-List-Element hook by generating a BACnet-Error reply. The BACnetSrvcErrorCbCompletion() completion routine should not be used for these services, since they must include the sequence number of the offending list-element in the reply.
Return: IEC_BACNET_STATUS
- InOut:
Scope
Name
Type
Comment
Return
BACnetChangeListErrorCbCompletionInput
phTransactionPOINTER TO BYTE
The handle recived in the hook callback function which identifies the current request in the API’s internal transaction state machine.
errClassVariable to hold BACnet Error Class information.
errCodeVariable to hold BACnet Error Code information
firstFailedThe first element in the received list which caused an error during processing the AddListElement or RemoveListElement service ist stored here. If no error occurred this shall be 0.