ETrigTlA (FB)¶
FUNCTION_BLOCK ETrigTlA IMPLEMENTS IFBCommand
Serves as a basis for Edge Triggered, Time limited, Abortable function blocks
- InOut:
Scope
Name
Type
Comment
Input
xExecute
BOOL
Rising edge: Action startsFalling edge: Resets outputsIf a falling edge occurs before the function block has completed its action, the outputs operate in the usual manner and are only reset if either the action is completed or in the event of an error. In this case, the corresponding output values (xDone
,xError
,iError
) are present at the outputs for exactly one cycle.xAbort
BOOL
TRUE
: Action is stopped immediately and all outputs are reset to their initial values.udiTimeLimit
UDINT
Defines how long (µs) an FB (requiring a long time for complete processing) may run until it is forced to return to the calling POU. The value 0 means that there is no time limitation.
Output
xDone
BOOL
TRUE
: Action successfully completedxBusy
BOOL
TRUE
: Function block activexError
BOOL
TRUE
: Error occurred, function block aborts actionFALSE
: No errorxAborted
BOOL
TRUE
: Action aborted by user