ETrigTl (FB)¶
FUNCTION_BLOCK ETrigTl IMPLEMENTS IFBCommand
Serves as a basis for Edge Eriggered, Time limited function blocks
- InOut:
Scope
Name
Type
Comment
Input
xExecuteBOOLRising edge: Action startsFalling edge: Resets outputsIf a falling edge occurs before the function block has completed its action, the outputs operate in the usual manner and are only reset if either the action is completed or in the event of an error. In this case, the corresponding output values (xDone,xError) are present at the outputs for exactly one cycle.udiTimeLimitUDINTDefines how long (µs) an FB (requiring a long time for complete processing) may run until it is forced to return to the calling POU. The value 0 means that there is no time limitation.
Output
xDoneBOOLTRUE: Action successfully completedxBusyBOOLTRUE: Function block activexErrorBOOLTRUE: Error occurred, function block aborts actionFALSE: No error