Creating Trace Configuration
For a complete trace configuration, specify at least one task and one variable. In order to trigger the data sampling, activate the trigger option and select a trigger variable or specify a recording condition.
Assigning tasks
In this task, the data sampling is executed at runtime. Usually the same task is selected where the variables are written.
Double-click the trace object.
The trace editor opens with the commands available in the menu.
Click .
The Trace Configuration dialog opens. In the Trace Record tree view, the top item is selected and the Record Settings subdialog is shown on the right.
In the Task list box, click the
symbol.The list box opens with all tasks that are available throughout the application.
Select a task for the trace.
Configuring a trace variable
Double-click the trace object.
The trace editor opens. The commands of the menu are available.
Click Add Variable.
The Trace Configuration dialog opens. The Variable Settings subdialog is displayed on the right.
In the input field of the Variable setting, click
and in the Input assistant dialog select a trace variable.The variable is configured for data sampling. The trace record tree and the display tree were extended by the variable.
Click the Add Variable link.
The trace record tree and the display tree receive a new variable. The settings of the variables are available on the right.
Select a trace variable.
Click OK to exit the dialog.
The variables are trace variables and are displayed in the trace variable list.
Deleting a trace variable
Double-click the trace object.
Click a variable in the trace record tree.
Click Delete Variable or press Del.
Click OK to exit the dialog.
The variable is removed from the trace variable list.
Tracing a parameter
Double-click the trace object.
Click Add Variable.
The Trace Configuration dialog opens. The Variable Settings subdialog is displayed on the right.
Click
(to the right of the Variable setting, on the left of the input field).Select the Parameter option in the list box.
Click
and select a parameter from the Input Assistant dialog.Configure how the parameter is displayed.
Click OK to exit the dialog.
The parameter will be traced and displayed in the trace variable list.
Configuring a trigger
Double-click the trace object.
The trace editor opens with the commands available in the menu.
Click .
The Trace Configuration dialog opens. The Record Settings subdialog is displayed on the right.
Select the Enable trigger check box.
Select the task in which the trend record is to be executed.
Select a variable from the Trigger variable field.
Click OK to exit the dialog.
The data sampling will be triggered.
The trigger time is displayed as a black line in the diagram at runtime.
Download the application and start it.
Click .
The trace configuration is loaded. After triggering, the runtime system saves the value graph of the trace variables. The data is displayed in the trace editor. The trigger time is displayed as a black line in the diagram.
Configuring the display of the time axis
Double-click a trace object.
Click the Configuration link above the configuration tree.
The Trace Configuration dialog opens.
Select Time axis in the display tree (below Presentation (Diagrams)).
The display settings of the time axis are shown on the right.
Edit the presets and click the Preview link.
The changes are seen in the coordinate system preview.
Click Y-axis in the display tree. The Y-axis item is below every configured diagram. Therefore, the display of the value axis is set for each diagram.
The Display Settings subdialog of the selected axis is displayed on the right.
Change the preset value.
The changes are applied in the coordinate system preview.
Click OK to exit the Trace Configuration dialog.
The display changes are visible in the affected diagrams.
Configuring the display of the trace variable
Double-click a trace object.
Click the Configuration link.
The Trace Configuration dialog opens.
Select a variable below Trace Record.
The Variable Settings subdialog of the selected variable is displayed on the right.
Change a setting, for example the Line type.
Click OK to exit the dialog.
The display changes are visible in the affected diagrams.
Configuring the buffer for data on the runtime
Double-click a trace object.
Click .
The Trace Configuration dialog opens. The Record Settings subdialog is displayed on the right.
Click Advanced.
The Advanced Trace Settings dialog opens.
Change the setting Measure in every n-th cycle or Recommended runtime buffer size (samples).
Click OK to exit the dialog.
The buffer settings are reconfigured. It is applied after the trace configuration is loaded to the RTS the next time.
Editing the trace configuration at runtime
Requirement: The application is running on the controller and a trace configuration is loaded.
Double-click a variable in the trace record tree.
The Trace Configuration dialog opens.
Change the color, for example.
The variable is displayed in the new color in the affected diagrams without interrupting the execution of the application.
Tip
If you change essential settings, for example a trace variable, then you must download the trace configuration to the controller again.