Implementing a Multitest POU
To implement many related test cases in only one test POU, you can use the pragma {attribute 'test' := 'multitest'}: You decorate a test POU with ETrigA behavior with this pragma. Additional information is reported when logging during the testing procedure. For example, the test result for each individual test case is reported and logged. Additional inputs and outputs are required for this.
Creating a framework for the test case
A test case is a function block which follows a specific scheme (Interface convention). To make it easier to follow the scheme, we recommend using the wizard. If you manually create a test case, then it should always derive from TM.BaseMultiTest (Obsolete Test POU Implementations).
Add the test case function block below an application or in the POU pool. To do this, click the Add Object → Unit Test command in the context menu.
The Add Unit Test dialog will open.
Specify the following parameters:
Name of POU:
TestCase_1Type: Extend TM.BaseMultiTest
Add optional methods
Add implementation template
Add explanatory commentsTest case category:
BasicTestsClick Add to confirm the dialog and save the project.
A new function block with the
prvAbort,prbCyclicAction,prvResetOutputs, andprvStartmethods will be created.
For more information, see the following: Add Unit Test
Implementing the test logic
In the declaration part of the test POU, declare an instance of the testee. The example tests a CTU standard POU.
{attribute 'test':='multitest'} {attribute 'testcasetimeout':='15000'} FUNCTION_BLOCK CTU_TestCases EXTENDS TM.BaseMultiTest VAR_INPUT END_VAR VAR_OUTPUT END_VAR VAR counter : CTU; // testee instance cycleCounter : INT; // independant test control variable END_VARIn the implementation part of the
prvStartmethod, initialize the testee. The example initializes the CTU via reset and, if necessary, initializes variables which are required for the testing procedure. TheprvStartmethod is called one time beforeprvCyclicAction.SUPER^.prvStart(); // mandatory - don't change // Initialize the testee counter(CU:=FALSE, RESET:=TRUE); // reset the counter; note: initialization per test case must be performed in prvCyclicAction // Initialize test control variable for first test case cycleCounter := 0;
Call the testee and check its result in the
prvCyclicActionmethod. TheprvCyclicActionmethod is called untilxDoneis set toTRUE. As a result, the testee can be called over multiple PLC cycles for each test case. The following example implements only one test case (CASE 0), but other test cases can easily be added according to this scheme.SUPER^.prvCyclicAction(); // mandatory - dont' change CASE diTestCaseIndex OF 0: // test case #0; add test cases as new CASEs IF xGetTestInfo THEN // initializate test case // define mandatory test case information wsTestCaseName := "Count from 0 to 5"; wsTestCaseCategories := "CTU"; diTestCaseTimeout := 500; xDone := TRUE; // signal test case initialization done ELSE IF (cycleCounter = 0) THEN // prepare test case counter(CU:=FALSE, RESET:=TRUE, PV:=5); // stimulate testee as long as we expect: 5 rising edges to count to 5 equals minimum 10 cycles ELSIF (cycleCounter < 10) THEN // check: counter limit not reached yet TM.Assert_Bool_IsFalse(THIS^, counter.Q, "Counter signaled limit reached prematurely"); TM.Assert_Word_Less(THIS^, 5, counter.CV, "Counter reached limit unexpectedly"); counter(CU:= (NOT counter.CU), RESET:=FALSE); // Trigger counter with rising edges xDone := FALSE; // signal test still running ELSE // check: counter reached limit TM.Assert_Bool_IsTrue(THIS^, counter.Q, "Counter did not signal limit reached"); TM.Assert_Word_Equal(THIS^, 5, counter.CV, "Counter did not reach limit"); xDone := TRUE; // mandatory: signal test completed END_IF IF xDone OR xError THEN cycleCounter := 0; // clean up for next test case ELSE cycleCounter := cycleCounter + 1; // count cycles END_IF END_IF ELSE IF diTestCaseIndex < 0 THEN // mandatory, signal number of test cases, if called with (diTestCaseIndex < 0) diTestCaseCount := 1; xDone := TRUE; ELSE // mandatory, don't remove: fail for invalid test case index wsInfo := "Invalid test case index"; iError := 2; END_IF END_CASEUninitialization of the test could be done in the
prvResetOutputsmethod, but it is not necessary in this example. Delete the method.No special code needs to be executed if the test times out. Delete the
prvAbortmethod.
Configuring the IEC unit test element
In Title, specify a test case name.
Example:
N_001_TestWhen the test is executed, the title will be displayed as the test case name.
In Device read timeout (ms), specify a time. Example:
5000Note: For each test case, the system waits at least for the test status and test result to be read. Moreover, the system waits when the application status is read when logging in.
Before reading variables, the system will wait until the timeout has elapsed.
In Login retries, specify the maximum number of attempts to establish online mode. Example:
3Click in the upper left of the Selected categories table.
An input field will be displayed.
Specify all categories which are called in this test case.
Example:
BasicTestsAll test function blocks decorated with the
'testcategory' := 'BasicTests'attribute will be called in this test case.
Executing a test script
Requirement: The test environment is prepared. The test project is open in the CODESYS Development System and the device settings and communication settings are configured. These required instructions are made by a preparatory test case in the test script.
The contents of the Generated Unit Tests folder are deleted in order to remove the generated POUs of a previous IEC unit test.
The project and the Libraries to test are searched for test tables. Then the function blocks for executing the test tables are generated in the Generated Unit Tests folder.
The project and the libraries that are listed on Libraries to test are searched for function blocks and programs that are marked as test.
Then, of the detected programs and function blocks, those are removed which are excluded by the test categories or the name.
The remaining programs and function blocks will be used in the test.
A backup of the original application is created.
The test cases are inserted as IEC code in
PLC_PRG. In the declaration and implementation, the added lines of code are marked withGenerated by IEC Unit Test.If the application is too large for the controller, then the tests are subdivided automatically into several smaller applications. One or more executable applications are generated.
The test is executed with the generated application(s).
The following steps are processed:
A test application is downloaded to the controller.
The test application is started.
The test cases are executed. If the string variable
sInfoorwsInfois used in the test function blocks, then its contents are included in the test report.The timeout is monitored.
The test result is checked and then sent to the test report.
The application is removed from the controller.
A test report is generated containing all test results.
Examples for the CODESYS Test Manager
Examples of test scripts with CODESYS Test Manager projects are included with the installation of CODESYS Test Manager Examples. See: Example: Test scripts for the Test Manager