Element: Test Action
Symbol: 
Function: The element contains the configuration of the test driver actions. Test actions are the actual functional contents of a test script.
When you select a test action in the test script, the editor opens with the Test Action and Extended Settings tabs.
Each test action consists of exactly one action of a test driver and its configuration. Each test action of a test driver has its own specific configuration options. You can also configure the call and evaluation of a test action on the Extended Settings tab. The symbol in the test script changes accordingly.
Settings displayed in the test script editor
Visualization in the Test Script | Extended Settings |
|---|---|
![]() | No extended settings enabled |
![]() | Always use enabled |
Symbol grayed out | Ignore event enabled |
| An expression is defined in Condition. |
| Max. retries set to 10 |
| At least one exception is entered in Expected Exceptions. |
Tab: Test Action
Title | Name of the test action Also displayed in the test script editor |
Action | Selected action The test driver is displayed in parentheses. Example: If the input field is empty, then the actions of all test drivers are displayed in the list below. You can filter the display by typing in a corresponding string. |
The test action is configured on the Configuration tab.
Input and output parameters of the test action are configured on the Parameters (<number of input parameters>/<number of output parameters>) tab.
Tip
The detailed description of the Configuration and Parameters tabs is located in the help for the test driver action in "Reference, User Interface → Test Actions".
Tab: Extended Settings
Execute even on previous failure |
In the test script, the action is indicated by an exclamation mark after the symbol:
|
Condition | Expression Evaluated at runtime The test action is executed only if the expression is true. If the expression is false, then the test action is skipped. Example: In the test script editor, a conditional test action is identified by displaying the condition in parentheses after the test action. Example: Note: If you use a test script variable in the expression, then you need to specify the variable with a placeholder operator. Example: |
Initial delay [ms] | Time span (in milliseconds) after which the test action starts |
Max. retries | Maximum number of repetitions until the action is evaluated with Succeeded Maximum value: An action is repeated until it is evaluated as Succeeded or the number of Max. retries is reached. The test action evaluated as Failed only then. A delay time can be specified in Retry after [ms]. |
Retry after [ms] | Delay time (in milliseconds) until the next retry starts |
Ignore failure |
|
Cancel test run on failure |
|
Cancel current call on failure |
|
Result variable | Test script variable which contains the result of the test of the test action This is also the declaration. Example: . Possible results
Example: |
Exception variable | Test script variable This is also the declaration. If an exception occurs during the test, then its name is stored in the variable. The variable is available for additional referencing (for example, in a Python script). |
Evaluate output parameter even on failure |
|
Expected exceptions are those that have to occur during test execution. The test action is evaluated with Succeeded only then. | |
Exception Type | Example:
|
Compare type | Example:
|
Exception message | Text While the test is running, the test is compared to the exception in order to check whether or not it is the expected exception. This takes into account which check type you selected in Match Message. Note: Variable substitution via |
Match Message | Example:
. Check types:
|
Add | Adds another exception to the end of the table |
Remove | Deletes the selected exception |
Clone | Duplicates the selected exception and adds it to the end of the table |
Inner | Adds a subordinate exception to the selected exception |




