Logical I/O of an F-Device
The PROFIsafe parameters of an F-Device are located in the editor of the logical I/Os of the F-Device:
Tab: Safe parameterization: i-parameters. These are the safety-oriented device parameters from PROFIsafe devices.
Tab: Safe Configuration: F-Parameters. These are the protocol parameters of PROFIsafe.
The variables that are used for the safety application to access the I/Os are defined on the I/O Mapping tab of the editor.
For a more detailed description of the editor and its tabs, refer to Device Editor of Logical I/Os.
F-Parameters
Which of the F-Parameters listed below are actually used depends on the device.
F_Check_SeqNr
V2 mode: A sequential number that is always to be included in the CRC2 generation
Not editable
F_Check_iPar
Manufacturer-specific use within a homogeneous system
Not editable
F_SIL
SIL which the user requires from the respective F-Device. It is compared with the manufacturer's specification.
Editable
F_CRC_Length
CRC length
Value: 3-byte CRC
F_Par_Version
Version number of F-Parameters/FSCT 3/1 operating mode
Preset value: V2 mode (only V2 is supported)
Editable
F_Block_ID
Identification of the type of parameter block
Not editable
F_Source_Add
Editable
F_Par_CRC
changes when there is a change toF_Source_Add
.
Caution
The user must ensure that the F-Host has a unique source address within the PROFINET network and PROFIBUS fieldbuses (even for several safety controllers in the same fieldbus).
For topology T2 when several safety controllers are below the same PROFIBUS/PROFINET master: The uniqueness of F_Source_Add
must be guaranteed in the entire PROFINET/PROFIBUS network.
Tip
The user must ensure through organizational means that the F_Source_Add
source address of each F-Device of an F-Host corresponds exactly to the source address of its F-Host.
F_Dest_Add
Unique target address of the F-Device in the PROFIsafe network.
If several F-Hosts are used for controlling a plant, it is recommended to give to all F-Devices a unique
F_Dest_Add
. To this end, it is recommended that the user makes a list with the ranges of values forF_Dest_Add
that are permissible for the individual hosts.
This must also be realized even in the case of failure to satisfy the prerequisite that each F-Device is connected to precisely one F-Host via the wiring and thus receives its F-Parameters only from this F-Host.
Editable
F_Par_CRC
changes when there is a change toF_Dest_Add
.
Caution
The user must ensure that all F-Devices have a unique destination address F_Dest_Add
within a PROFINET network or PROFIBUS fieldbus (even for several safety controllers in the same network).
Tip
The user must make sure that the F_Dest_Add
on the Safe Configuration tab corresponds to the setting on the address switch of the F-Device (usually a DIP switch).
F_WD_Time
Time specification (in milliseconds) for the watchdog timer that monitors the duration until the receipt of the next valid PROFIsafe message.
Default value of the GSD file: Maximum processing time of the F-Device
Editable
F_Par_CRC
changes when there is a change toF_WD_Time
.
F_iPar_CRC
CRC that is calculated from the i-Parameters of the F-Device.
F_Par_CRC
changes when there is a change toF_iPar_CRC
.
Tip
As the value of F_iPar_CRC, the value of the CRC must be entered manually by means of the i-Parameters of the F-Device. The CRC for the i-Parameters is located on the Safe parametrization tab of the logical I/O of the F-Device or in the respective F-Device manufacturer-specific tool.
F_Par_CRC
CRC for all F-Parameters
Calculation by safe editors
This ensures the error-free transmission of the F-Parameters.
Not editable