Command: Scan for Devices

Dialog: Scan Devices

Table 11. Scanned Devices

Device name, Device type, Address, Station name, etc.

Data about the scanned device depending on network type.

When you change a value in the list of scanned devices, the value is displayed in italics. This indicates that the new value has been changed in the editor in CODESYS, but not in the device. When you download the value to the device, it is displayed normally.

Values which indicate differences between the project and the scanned device are displayed in orange.

If multiple device descriptions are available for the scanned device, then the name is displayed in bold. The selection of the matching device description is resolved differently for different fieldbuses. For more detailed information, see the corresponding fieldbus chapters.

If a device description cannot be found, then the following message is shown: "Attention! The device was not found in the repository." Depending on the bus system, additional information is displayed, such as vendor number and product number. The device cannot be inserted into the project without the installed device description.

Show differences to project

standard icon: The table in the dialog also shows additional configured devices (in the device tree of the project).

_cds_icon_option_deactivated.png: The table shows all scanned devices. The configured devices are not shown.

Scan for Devices

Starts a new search.

Copy All Devices to Project

The device which is selected in the table is inserted into the device tree in the project. If nothing is selected, then all scanned devices are shown.



Important

If you use Copy All Devices to Project to insert devices, which are available in the device tree, to the device tree, then the following should be noted: The data of the Process Data and <...> I/O Mapping tabs of the existing devices may be overwritten with the data of the recently inserted devices.

Table 12. Configured Devices

This part of the dialog is visible only when you select the Show differences to project option.

Differences between the scanned and configured devices are color-coded. Devices displayed in green are identical on both sides. Devices displayed in red are available only in the view of the scanned or configured devices.

_cds_icon_scan_copy_before.png

If you have selected a device in both views, then the scanned devices are inserted above the selected configured device.

_cds_icon_scan_copy_below.png

If you have selected a device in both views, then the scanned devices are inserted below the selected configured device.

_cds_icon_scan_change_device.png

If you have selected a device in both views, then the configured devices are replaced by the selected scanned device.

_cds_icon_scan_copy_all.png

All scanned devices are copied to the project.

_cds_icon_scan_delete.png

Deletes the selected configured device.



Special settings for PROFIBUS

Scan for Devices

New search for devices in the PROFIBUS Master network.

Copy All Devices to Project

Copies all selected slaves into the project. Existing slaves with the same address are overwritten.

State

Scanned and projected slaves are assigned by station address.

  • _pbdp_icon_state_ok.png: The detected device matches the configured device.

  • _pbdp_icon_state_new.png: No device was detected with the same station address.

  • _pbdp_icon_state_error.png: Assignment of the detected device to the configured device is possible, but the module configuration is different.

Unique assignment to the devices of a specific manufacturer is not possible with the available information (ID number for slaves, I/O configuration for modules). The Add Device dialog opens where you can assign the scanned devices manually to the devices available in the project.