Tab: EtherCAT Slave – Online

The tab provides slave status information and functions for the file transfer to the slave via EtherCAT (FoE).

Requirement: The expert settings for the slave are selected and the application is logged in to the controller.

Table 34. State machine

Init

Use for debugging purposes

Bootstrap

The slave is switched to Bootstrap Mode.

Required if firmware files should be transferred to or from the slave

Pre-Op

Use for debugging purposes

Safe-Op

Use for debugging purposes

Op

Use for debugging purposes

Current status

Requested status



Table 35. DLL status

Port A

Port B

Port C

Port D

  • No Carrier / Open: No carrier signal exists at the port, but the port is open.

  • No Carrier / Closed: No carrier signal exists at the port and the port is closed.

  • Carrier / Open: A carrier signal exists at the port and the port is open.

  • Carrier / Closed: A carrier signal exists at the port, but the port is closed.

Note: If the function is not supported, then the status can be hidden.



Table 36. File Access over EtherCAT

Download

Download of firmware files

A dialog opens to save the firmware file. In this dialog, the input of a string as well as a password is necessary in order to execute the file transfer. The information should be taken from the data sheet of the slave.

Upload

Upload of firmware files

A dialog opens to open the firmware file. In this dialog, the input of a string as well as a password is necessary in order to execute the file transfer. The information should be taken from the data sheet of the slave.



Table 37. E²PROM access

Write E²PROM

Writes the configuration of the slave to the E²PROM.

A dialog for storing the configuration opens in the same way as for File access over EtherCAT.

Read E²PROM

Reads the configuration of the slave from the E²PROM.

Upload of firmware files

A dialog for opening the configuration opens in the same way as for File access over EtherCAT.

Write E²PROM XML

Transfers the first 16 bytes from the ESI-XML file to the E²PROM. These contain the basic configuration of the slave.

The command can be executed only when configuration data exists in the XML file (<ConfigData> section).