Variable Configuration – VAR_CONFIG
You use the "variable configuration" to map variables of functions blocks to the process image. For declarations in the function block, you assign the variables to the device inputs/outputs without providing the full address. Then, the exact address is provided centrally for all function block instances of the application in a global variable list including VAR_CONFIG declarations. This global variable list with the VAR_CONFIG declarations is called the variable configuration.
Important
For changes to variables that are assigned to I/O addresses, CODESYS displays them immediately in the process image. For changes to variables that are mapped by a variables configuration, CODESYS displays them only at the end of the responsible task.
Declaration of variables in functions blocks
When declaring variables in a function block, you declare the variables between the keywords VAR and END_VAR and assign incomplete addresses to the variables. In doing so, you assign incomplete addresses to the variables. You mark these incomplete addresses with an asterisk (*).
Syntax:
<identifier> AT %<I\|Q>*:<data type>;
You define two local I/O variables: the input variable xLocIn and the output variable xLocOut.
FUNCTION_BLOCK locio VAR xLocIn AT %I*: BOOL := TRUE; xLocOut AT %Q*: BOOL; END_VAR
The final definition of the addresses is performed in the variable configuration in a global variable list.
In the global variable list that you use as the variable configuration, you define the variable declarations with the absolute addresses between the VAR_CONFIG and END_VAR keywords.
You must declare the VAR_CONFIG variables with the complete instance path, separating the individual POU and instance name by a dot. The declaration has to include an address whose class (input/output) matches the class of the incomplete address (%I*, %Q*) in the function block. The data type also has to match.
Syntax:
<instance variable path> AT %<I\|Q><location>: <data type>;
If the path instance does not exist, then an error is reported. CODESYS issues an error also if there is not an address configuration available for a variable that you declared with an incomplete address.
The locio function block in the example above is used in a program as follows:
PROGRAM PLC_PRG VAR locioVar1: locio; locioVar2: locio; END_VAR
A correct variable configuration in a global variable list could then look like this:
VAR_CONFIG PLC_PRG.locioVar1.xLocIn AT %IX1.0 : BOOL; PLC_PRG.locioVar1.xLocOut AT %QX0.0 : BOOL; PLC_PRG.locioVar2.xLocIn AT %IX1.0 : BOOL; PLC_PRG.locioVar2.xLocOut AT %QX0.3 : BOOL; END_VAR
Creating a variable configuration
Requirements: You have a project open that includes a PLC configuration with a field device. The project contains a program (for example, PLC_PRG) and a function block (for example, func1). The field device has inputs and outputs. The textual view is selected in the options for the declaration editor.
In the function block, assign variables to device I/Os with incomplete addresses and then create a variable configuration.
Double-click a function block in the device tree (for example,
func1).The POU editor opens.
In the declaration part, specify
xLocIn AT %I*: BOOL := TRUE;between theVARandEND_VARkeywords andXLocOut AT %Q*:BOOL;in the next line.You have declared an input variable
xLocInand assigned it to the incomplete input address%I*of a field device. You have assigned the declared output variables have to the incomplete output address%Q*.Click the
PLC_PRGobject in the device tree and add the following to the declaration part of the program betweenVARandEND_VAR:locioVar1: func;locioVar2: func;In the device tree, right-click the Application object and click , and then in the Add Global Variable List dialog click Add.
The global variable list is added to the device tree and opens in the editor.
Change the keyword
VAR_GLOBALtoVAR_CONFIG.Click .
The following instance paths are added:
PLC_PRG.logioVar1.xLocIn AT %I*; PLC_PRG.logioVar2.xLocIN AT %I*; PLC_PRG.logioVar1.xLocOut AT %Q*; PLC_PRG.logioVar2.xLocOut AT %Q*;
Now, replace the incomplete addresses
%I*and%Q*with the absolute, complete addresses.