Skip to main content

Data Type: ANY, ANY_<type>

The data types ANY or ANY_<type> are used in interfaces of functions, function blocks, or methods in order to type input parameters whose type is unknown or unspecified: The input variables (VAR_INPUT) have a generic data type.

The compiler replaces the type of input variable internally with the data structure described below, whereby the value is not passed directly. Instead, a pointer is passed to the actual value so only a variable can be passed. Therefore, the data type is only specified when it is called. As a result, calls of such POUs can be made using arguments which each have different data types.

Tip

Literals, replaced constants, and results of function calls or expressions cannot be passed to input variables (VAR_IN_OUT).

Internal data structure for ANY and ANY_<type>

When code is compiled, the input variables are typed internally with ANY data type by the following structure. When the POU is called (at runtime), the argument is passed to a reference parameter.

TYPE AnyType :
STRUCT
    // Type of the current parameter
    typeclass : __SYSTEM.TYPE_CLASS ;
    // Pointer to the current parameter
    pvalue : POINTER TO BYTE;
    // Size of the data to which the pointer points
    diSize : DINT;
END_STRUCT
END_TYPE

Tip

You can access the input variable within the POU via this structure by means of this structure, and for example query the passed value.

Example 218. Example

This compares whether or not two input variables have the same type and the same value.

FUNCTION funGenericCompare : BOOL
// Declaration
VAR_INPUT
        any1 : ANY;
        any2 : ANY;
END_VAR
VAR
        pTest : POINTER TO ARRAY [0..100] OF POINTER TO DWORD;
        diCount: DINT;
END_VAR

// Implementation
pTest := ADR(any1);
Generic_Compare := FALSE;
IF any1.typeclass <> any2.typeclass THEN
        RETURN;
END_IF
IF any1.diSize <> any2.diSize THEN
        RETURN;
END_IF
// Byte comparison
FOR iCount := 0 TO any1.diSize-1 DO
        IF any1.pvalue[iCount] <> any2.pvalue[iCount] THEN
                RETURN;
        END_IF
END_FOR
Generic_Compare := TRUE;
RETURN;


Declaration

The syntax descriptions refer to a POU with exactly one parameter (an input variable).

Syntax

<scope> <POU name> : <data type of return value>
VAR_INPUT
    <variable name> : <generic data type>;
END_VAR

<scope>

Possible scopes:

  • FUNCTION

  • FUNCTION_BLOCK

  • METHOD

<POU name>

Name of the POU

: <data type of return value>

Optional

<variable name>

Name of the input variable

<generic data type>

ANY, ANY_BIT, ANY_DATE, ANY_NUM, ANY_REAL, ANY_INT, or ANY_STRING

Example 219. Example
FUNCTION funComputeAny : BOOL
VAR_INPUT
    anyInput1 : ANY; // For valid data type see table
END_VAR

FUNCTION_BLOCK FB_ComputeAny
VAR_INPUT
    anyInput1 : ANY;
END_VAR

FUNCTION_BLOCK FB_ComputeMethod
METHOD methComputeAnny : BOOL
VAR_INPUT
    anyInput1 : ANY_INT; // Valid data types are SINT, INT, DINT, LINT, USINT, UINT, UDINT, ULINT
END_VAR


Tip

With compiler versions > 3.5.1.0, the generic IEC data types in the table are supported.

The table represents the hierarchy of the generic data types and provides information as to which generic data type of the formal parameter (declaration) allows which elementary data types of the argument (call).

Generic data type in the case of a formal parameter

Allowed elementary data type in the case of an actual parameter (argument)

ANY

ANY_BIT

  • BYTE

  • WORD

  • DWORD

  • LWORD

ANY_DATE

  • DATE

  • DATE_AND_TIME, DT

  • TIME_OF_DAY, TOD

  • LDATE

  • LDATE_AND_TIME, LDT

  • LTIME_OF_DAY, LTOD

ANY_NUM

ANY_REAL

REAL, LREAL

ANY_INT

USINT, UINT, UDINT, ULINT

SINT, INT, DINT, LINT

ANY_STRING

STRING, WSTRING

Call

The syntax descriptions refer to a POU with exactly one parameter, to which an argument is passed. As a result, the data type of the argument specifies the generic data type of the input variable. For example, arguments of the type BYTE, WORD, DWORD, LWORD can be passed to a type ANY_BIT input variable.

Syntax of function call:

<name of function> (<argument>)

Syntax of function block call

<name of function block instance> (<name of input variable> := <argument>)

Syntax of method call

<name of function block instance> . <name of method> (<name of input variable> := <argument>)

<argument>

Transfer variable

Example 220. Example
PROGRAM PLC_PRG
VAR
    byValue : BYTE := 16#AB;
    iValue : INT := -1234;
    xResultByte : BOOL;
    xResultInt : BOOL;

    fbComputeAnyByte : FB_ComputeAny;
    fbComputeAnyInt : FB_ComputeAny;

    fbComputeM1 : FB_ComputeMethod;
    fbComputeM2 : FB_ComputeMethod;

    byN : BYTE := 1;
    wBitField1 : WORD := 16#FFFF;
    wBitField2 : WORD := 16#0001;
    xInit : BOOL;
    xResult : BOOL;
END_VAR

//Implementation
xResultByte := funComputeAny(byValue);
xResultInt := funComputeAny(iValue);

xResult := funGenericCompare(wBitField1, wBitField2);

fbComputeAnyByte(anyInput1 := byValue);
fbComputeAnyInt(anyInput1 := iValue);

fbComputeM1.methComputeAnny(anyInput1 := byValue);
fbComputeM2.methComputeAnny(anyInput1 := iValue);