RAMP_INT (FB)¶
FUNCTION_BLOCK RAMP_INT
Limits the slope of a value to a certain value
The limitation of the slope is given by the maximum ascend ASCEND and the maximum descend DESCEND and a time base
TIMEBASE defining the time for which ASCEND or DESCEND hold.
Bemerkung
It is not necessary to readjust the controller parameters (KP, TN, TV) if the cycle time changes.
Example
- InOut:
Scope
Name
Type
Comment
Input
ININTInput value
ASCENDINTLimitation of acceleration: Maximum ascent per time base Example:
ASCEND := 25andTIMEBASE := T#1s=> Maximum ascent of 25 increments per secondDESCENDINTLimitation of deceleration: Maximum descent per time base (
DESCEND> 0) Example:DESCEND := 20andTIMEBASE := T#500ms=> Maximum ascent of 20 increments in 500 millisecondsTIMEBASETIMEReference forASCEND/DESCEND:t#0s :ASCEND/DESCENDdefined per callelse :ASCEND/DESCENDdefined per specified timeIfTIMEBASE = t#0s, then the time base is equal to the task cycle time. In this case the limitation refers to a task cycle.Usually this corresponds exactly to one call of the function blockRAMP_INT.Bemerkung
If the time base
TIMEBASEis smaller than the task cycle time, then this will lead to a violation of the sampling theorem and might result in a loss of information in the output signal.RESETBOOLReset of the function blockTRUE: Stops the internal calculation and reinitializes the function block.The last calculated output value inOUTis maintained in order to start the internal calculation with it at the next restart of the function block.FALSE: Outputs the smoothed input signal at outputOUT.Output
OUTINTFunction value with limited ramp The value gets stored internally and will be used for the calculation of the ascent and the descent of the input signal.