SA0095:条件分配
检测条件下的分配 IF, CASE, 或者 REPEAT 结构体
理由:赋值 (:=) 和比较 (=) 很容易被误解。结果,条件中的分配很容易是无意的,因此会被报告。这也会使代码的读者感到困惑。
重要性:高
例 88. 例子
PROGRAM PLC_PRG
VAR
iCond1:INT := INT#1;
iCond2:INT := INT#2;
xCond:BOOL := FALSE;
iVar : INT;
END_VARIF INT_TO_BOOL(iCond1 := iCond2) THEN // SA0095
iCond1 := INT#1;
iCond2 := INT#2;
ELSIF (iCond1 := 11) = 11 THEN // SA0095
iCond1 := INT#1;
iCond2 := INT#2;
END_IF
IF xCond := TRUE THEN // SA0095
xCond := FALSE;
END_IF
IF (xCond := FALSE) OR (iCond1 := iCond2) = 12 THEN // SA0095
xCond := FALSE;
iCond1 := INT#1;
iCond2 := INT#2;
END_IF
IF (iVar := iVar + 1) = 120 THEN // SA0095 (can be valid, but is not reparable very well
iVar := 0;
END_IF
WHILE (xCond = TRUE) OR (iCond1 := iCond2) = 12 DO // SA0095
xCond := FALSE;
END_WHILE
//Error: assignment in repeat loop
REPEAT
xCond := FALSE;
UNTIL (xCond = TRUE) OR (iCond1 := iCond2) = 12 // SA0095
END_REPEAT 输出在 留言 看法:
SA0095:条件分配:“...”