Skip to main content

运行时配置 (CIFX)

对于 CIFX 版本,必须在 PROFINET 配置文件 (*.cfg)。在配置文件中,可以配置 CIFX 固件的其他设置,例如加载另一个固件版本(见注释)。

[ComponentManager]
...
Component.7=CmpHilscherCIFX

[CmpHilscherCIFX]
InterruptMode=1                        ; available e.g. for RTE or Linux, not for WinPLC !
DMAMode=1                              ; increases Performance on RTE

DynamicFirmware=1                      ; driver loads default firmware, for Profinet this is "cifxpnm.nxf", which is the V3.x
…
;Device.1.BootloaderFilePath=$Firmware$\HilscherCIFX\Firmware\NETX100-BSL.bin
;Device.1.Channel.0.FirmwareFile=$Firmware$\HilscherCIFX\Firmware\cifxpnm2.nxf   ; this is the V2.x firmware for the legacy CIFX controller !