SendSMS (FB)¶
FUNCTION_BLOCK SendSMS EXTENDS CBM.ETrigTo
By use of this function block, a short message with the provided information will be send.
After starting this function block, it will try to allocate the modem.
When it is free a lock is set and therefore reserved for the currently function block.
After a reset (falling edge on “xExecute”) the lock is released.
- InOut:
- Scope - Name - Type - Comment - Inherited from - Input - xExecute- BOOLRising edge: Action startsFalling edge: Resets outputsIf a falling edge occurs before the function block has completed its action, the outputs operate in the usual manner and are only reset if either the action is completed or in the event of an error. In this case, the corresponding output values (- xDone,- xError) are present at the outputs for exactly one cycle.- ETrigTo - udiTimeOut- UDINT- Defines the time (µs) after which an FB (e.g. requiring an external acknowledgement) aborts operation due to a timeout with error message. - ETrigTo - Output - xDone- BOOL- TRUE: Action successfully completed- ETrigTo - xBusy- BOOL- TRUE: Function block active- ETrigTo - xError- BOOL- TRUE: Error occurred, function block aborts action- FALSE: No error- ETrigTo - Inout - ModemFB- The modem function block - Input - smsInfo- The neccessary information to send a short message. - Output - eError- error - VisuResult- This output is needed for the visualization. 