IOL_EventCode_Port (ENUM)

TYPE IOL_EventCode_Port :

Master/Port EventCode:

Attributes:
qualified_only
InOut:

Name

Initial

Comment

No_malfunction

16#0

No malfunction

Process_Data_mismatch

16#17FF

Process Data mismatch – check submodule configuration (Source: Clause 7 PROFINET Lifecycle manager)

No_Device

16#1800

No Device (Source: SMI_PortEvent)

Startup_parameterization_error

16#1801

Startup parameterization error – check parameter (Source: Clause 7 PROFINET Lifecycle manager)

Incorrect_VendorID

16#1802

Incorrect VendorID – Inspection Level mismatch (Source: SMI_PortEvent)

Incorrect_DeviceID

16#1803

Incorrect DeviceID – Inspection Level mismatch (Source: SMI_PortEvent)

Short_circuit_at_CQ

16#1804

Short circuit at C/Q – check wire connection (Source: SMI_PortEvent)

PHY_overtemperature

16#1805

PHY overtemperature – check Master temperature and load (Source: SMI_PortEvent)

Short_circuit_at_L

16#1806

Short circuit at L+ – check wire connection (Source: SMI_PortEvent)

Overcurrent_at_L

16#1807

Overcurrent at L+ – check power supply (e.g. L1+) (Source: SMI_PortEvent)

Device_Event_overflow

16#1808

Device Event overflow

Backup_inconsistency_memory_out_of_range

16#1809

Backup inconsistency – memory out of range (2048 octets) (Source: SMI_PortEvent)

Backup_inconsistency_idendity_fault

16#180A

Backup inconsistency – idendity fault (Source: SMI_PortEvent)

Backup_inconsistency_Data_storage_unspecific_error

16#180B

Backup inconsistency – Data storage unspecific error (Source: SMI_PortEvent)

Backup_inconsistency_upload_fault

16#180C

Backup inconsistency – upload fault (Source: SMI_PortEvent)

Parameter_inconsistency_download_fault

16#180D

Parameter inconsistency – download fault (Source: SMI_PortEvent)

P24_missing_or_undervoltage

16#180E

P24 (Class B) missing or undervoltage

Short_circuit_at_P24

16#180F

Short circuit at P24 (Class B) – check wire connection (e.g. L2+)

Short_circuit_at_IQ

16#1810

Short circuit at I/Q – check wiring

Short_circuit_at_CQ_of_DO

16#1811

Short circuit at C/Q (if digital output) – check wiring

Overcurrent_at_IQ

16#1812

Overcurrent at I/Q – check load

Overcurrent_at_CQ_of_DO

16#1813

Overcurrent at C/Q (if digital output) – check load

Invalid_cycle_time

16#6000

Invalid cycle time (Source: SMI_PortEvent)

Revision_fault

16#6001

Revision fault – incompatible protocol version (Source: SMI_PortEvent)

ISDU_batch_failed

16#6002

ISDU batch failed – Parameter inconsistency? (Source: SMI_PortEvent) Notification_Port_status_changed := 16#FF26, //Notification Port status changed ‒ Use “SMI_PortStatus” service to read Port status in detail