ControllerState (ENUM)¶
TYPE ControllerState :
- Attributes:
qualified_only
- InOut:
Name
Initial
Comment
NotInit
0
Not initilaized
Init
Initialized
Open
Ethernet Adapter is open
WaitCheckStationname
Controller is currently checking if it’s stationname is used by another device
WaitCheckIP
Controller is currently checking if it’s IP address is already used by other device
Run
Controller is running
Stopped
Controller is running, but does not connect to slaves
Error
16#100
unspecified error
ErrorLicenceCheck
error checking licence
ErrorControllerStationname
Controller stationname is already used by another device
ErrorControllerIP
Controller IP address is already used by another device
ErrorNoIP
Ethernet Adapter’s IP address is 0.0.0.0 (not plugged ?)
ErrorGetIP
internal error reading IP address
ErrorInitRPC
internal error initialising RPC layer. Maybe unabale to open UDP - Port ?
ErrorFindEthernet
specified ethernet adapter (Interface-name) was not found.
ErrorEthernet
internal error activating SysEthernet runtime-interface
ErrorNoLicence
no valid licence (or demo mode expired)
ErrorIPNotMatching
currently active IP does not match the controller’s configuration