ClientRequestReadWriteMultipleRegistersWide (FB)¶
FUNCTION_BLOCK ClientRequestReadWriteMultipleRegistersWide EXTENDS ModbusFB.ClientRequest
ReadWriteMultipleRegister client request (FC23) for registers > 16bit.
For details about client request see |ClientRequest|. For details about “wide registers” and endianess see ServerTCP_extended or ServerSerial_extended.
Please note: The write operation is performed before the read.
Please visit https://forge.codesys.com/prj/codesys-example/modbus/home to find examples.
- InOut:
Scope
Name
Type
Initial
Comment
Inherited from
Input
xExecuteBOOLRising edge: Starts defined operationFALSE: Resets the defined operation after ready condition was reachedETrigTo
udiTimeOutUDINTMax. operating time for executing [µs], 0: No operating time limit
ETrigTo
Output
xDoneBOOLReady condition reached
ETrigTo
xBusyBOOLOperation is running
ETrigTo
xErrorBOOLError condition reached
ETrigTo
Inout
rClientClientReference to |Client|.
ClientRequest
Input
uiUnitIdUINT0
Unit-Id to send the request to.
ClientRequest
udiReplyTimeoutUDINT(50 * 1000)
50 ms
ClientRequest
uiMaxRetriesUINT0
Maximum number of request retries in case of “reply timeout”.
ClientRequest
Output
eErrorIDErrorError status
ClientRequest
eExceptionExceptionCodesRequest exception code.
ClientRequest
uiRetryCntUINT0
Number of request retries in case of “reply timeout”.
ClientRequest
Input
uiWriteStartItemUINT0
First “data item” to write.
uiWriteQuantityUINT1
Number of “data items” to write.
pWriteDataPOINTER TO BYTE
0
Pointer to write data.
uiWriteDataItemSizeUINTwrite “data item” size / register width (in bytes). The ClientRequest has to know about the “data item” size a-priori to provide memory for result data. In case the server unexpectedly does have a different “data item” size than assumed, the ClientRequest can not succeed.
uiReadStartItemUINT0
First “data item” to read.
uiReadQuantityUINT1
Number of “data items” to read.
pReadDataPOINTER TO BYTE
0
Pointer to read data.
uiReadDataItemSizeUINTread “data item” size / register width (in bytes).