MQTTParam (PARAMS)ΒΆ
- Attributes:
- qualified_only
- InOut:
- Scope - Name - Type - Initial - Comment - Constant - g_uiMaxTopicLevel - UINT- 10 - The maximal count of levels per topic - g_udiMaxQueuedPackets - UDINT- 1000 - The maximal count of queued packets that are possible to store - g_udiMaxPacketSize - UDINT- 6000 - Maximum size of a MQTT packet byte array, MUST be smaller than 256 MB ! - g_udiMaxReceiveBufferSize - UDINT- g_udiMaxPacketSize - Maximum size of the receive buffer. This value should be large enough to store the packets to be received per one cycle. - g_udiMaxPayloadSize - UDINT- 4096 - Maximum size of a MQTT payload byte array, MUST be < than max. Packet Size ! - g_udiMaxPublishersAndSubscribers - UDINT- 20 - Maximum number of publishers + subscribers - g_udiMaxUserProperties - UDINT- 10 - Maximum number of user properties per packet (MQTT V5 only) - g_udiMaxUserPropertyValueLength - UDINT- 80 - Maximum length of the user property key and value (MQTT V5 only, Range: 1 - 1024)) - g_udiMaxCorrelationDataSize - UDINT- 256 - Maximum size of the correlation data (MQTT V5 only) - g_udiMaxAuthDataSize - UDINT- 256 - Maximum size of the authentication data (MQTT V5 only) 