ModbusTCP_Parameter (PARAMS)ΒΆ
- InOut:
- Scope - Name - Type - Initial - Comment - Constant - MAX_MODBUS_CHANNELS - UINT- 100 - RESPONSE_TIMEOUT_DELAY - TIME- TIME#2s0ms - CONNECTION_ATTEMPT_DELAY - TIME- TIME#1m0s0ms - Minimum time after connection attempt before a new connection attempt can be made on a specific line of the Server.(Only used for redundancy purposes) - SWITCH_ATTEMPT_INTERVAL - TIME- TIME#10s0ms - Minimum time after switch attmept before another switch attempt can be made for the Server.(Only used for redundancy purposes) - SEND_INACTIVE_INTERVAL - TIME- TIME#5s0ms - Minimum time between 2 checks on the inactive line of the Server. Only needed if both lines are configured to be connected at all times.(Only used for redundancy purposes)