AdapterState (ENUM)ΒΆ
TYPE AdapterState :
Possible states of a RemoteAdapter (device under scanner).
- Attributes:
qualified_only- InOut:
Name
Initial
Comment
DISABLED
0
Disabled in device tree.
NOT_CONFIGURED
State after download going on with |IP_CONFIG| after setting values to default.
IP_CONFIG
Setting IP address and port. |BUS_ERROR| if IP address not valid. Going on with |ENCAPSULATION_CONFIG| if ok.
ENCAPSULATION_CONFIG
Opens the TCP port to the client and if there is no error go to |LIST_SERVICES|, else |BUS_ERROR|.
LIST_SERVICES
Empty state going on with |REGISTER_SESSION|.
REGISTER_SESSION
Register Session message is send and response is evaluated. If error |BUS_ERROR|, else |PARAMETER_CONFIG|.
PARAMETER_CONFIG
UserParameters are going to be sent. If error occurred, a logmessage is generated and no matter what the next state is AdapterState.CONFIGURED.
CONFIGURED
Forward Open is processed here going on with |RUNNING| if success and join multicast address if necessary, else retrying Forward Open in this state.
RUNNING
All connections established. IO data will be sent to the slave.
RESET
Performing a reset triggered on the input of the RemoteAdapter.
RESET_SERVICE
Reset service of CIP is triggered over the network.
BUS_ERROR
If connection is lost and AUTO_RESET is disabled in the configurator or problems with sockets occurred, this state gets active.
ERROR
Downloaded parameter are inconsistent or no memory or connection problems