PB_CNCT (FB)¶
FUNCTION_BLOCK PB_CNCT
This function block can be used for establishing a DPV1 Class 2 connection to a PROFIBUS Slave. The connection is established and kept open if input REQ = TRUE, it’s closed when REQ = FALSE. While the connection is in state open, the ID output has a value that can be used as ID input of RDREC or WRREC.
- InOut:
- Scope - Name - Type - Initial - Comment - Input - REQ- BOOL- Start Request - MASTER- BYTE- Master ID - SEGMENT- BYTE- Always set to 0. - STATION- BYTE- Station address of the target - SLOT- BYTE- Slot number of the target - Output - VALID- BOOL- Connection is valid - ERROR- BOOL- Error detected - BUSY- BOOL- FB is busy - STATUS- DWORD- Last detected status - ID- DWORD- CommFB.Constants.INVALID_ID - Identifier of a PB Slave. Use for RDREC or WRREC (Class 2) 