Generic_Service (FB)ΒΆ
FUNCTION_BLOCK Generic_Service EXTENDS BaseService
This function block performs a generic service at an EtherNet/IP Adapter. The message will be sent as an unconnected explicit message request.
Note
Data received and send needs to be swapped. See parent folder.
/// Force trigger to TRUE to activate.
/// Example device used here is WAGO 750-352 FC ETHERNET.
/// But you can adapt it, by using the services which are implemented by your prefered device.
PROGRAM PLC_PRG
VAR
dut : ENIP.Generic_Service ;
data: usint:=16#FF;
trigger: BOOL;
END_VAR
dut.xExecute := trigger;
dut.itfEtherNetIPDevice := WAGO_750_352_FC_ETHERNET;
dut.eClass := 100;
dut.dwInstance := 1;
dut.wAttribute := 11;
dut.eService := ENIP.CIPCommonService.SET_ATTRIBUTE_SINGLE;
dut.pWriteData := ADR(data);
dut.udiWriteDataSize := 1;
dut();
- InOut:
Scope
Name
Type
Comment
Inherited from
Input
xExecuteBOOLRising edge: Action startsFalling edge: Resets outputsIf a falling edge occurs before the function block has completed its action, the outputs operate in the usual manner and are only reset if either the action is completed or in the event of an error. In this case, the corresponding output values (xDone,xError) are present at the outputs for exactly one cycle.ETrig
Output
xDoneBOOLTRUE: Action successfully completedETrig
xBusyBOOLTRUE: Function block activeETrig
xErrorBOOLTRUE: Error occurred, function block aborts actionFALSE: No errorETrig
Input
itfEtherNetIPDeviceIEtherNetIPServiceBaseService
eClassBaseService
dwInstanceDWORDBaseService
tTimeOutTIMEBaseService
Output
eErrorBaseService
Input
wAttributeWORDAttribute the services is addressed to. Leave 0 if this service does not address an attribute.
eServiceChoose one of the CIPCommonService members, or insert any vendor specific service code.
pWriteDataPOINTER TO BYTE
Data to write to the EtherNet/IP Adapter. Leave 0 if no data should be sent to the EtherNet/IP Adapter.
udiWriteDataSizeUDINTSize of data to write to the EtherNet/IP Adapter. Leave 0 if no data should be sent to the EtherNet/IP Adapter.
pReadDataPOINTER TO BYTE
Data expected to receive from the EtherNet/IP Adapter. Leave 0 if no data is expected to be received from the EtherNet/IP Adapter.
udiReadDataSizeUDINTSize of data expected to receive from the EtherNet/IP Adapter. Leave 0 if no data is expected to be received from the EtherNet/IP Adapter.
Output
udiReceivedDataSizeUDINTSize of the received data