Get_Attribute_Single (FB)ΒΆ
FUNCTION_BLOCK Get_Attribute_Single EXTENDS BaseService
Use this function block for querying the attribute of a specific instance of a CIP object.
Note
Data received and send needs to be swapped. See parent folder.
(* CIP Data type for string with a length of max. 64 chars *)
TYPE STRING64 :
STRUCT
   uiLength   : UINT;
   sString    : STRING(63);
END_STRUCT
END_TYPE
PROGRAM PLC_PRG
VAR
    strHostnameToGet   : STRING64;
    getAttributeSingle : ENIP.Get_Attribute_Single ;
    udiReceivedData    : UDINT;
END_VAR
getAttributeSingle(
    xExecute:= ,
    itfEtherNetIPDevice:= EtherNetIP_Adapter,    (* instance of the device (instance is found in the I/O Mapping of the device) *)
    eClass:= ENIP.CIPClass.TCPIPInterfaceObject, (* cip class which contains the desired attribute *)
    dwInstance:= 1,                              (* value of 0 is class level, range from 1..x is instance level *)
    wAttribute:= 6,                              (* attribute no. 6 of the tcp/ip interface object is the Hostname (CIP Spec. Vol.2 Chapter 5-3.3.2.6)*)
    pData:= ADR(strHostnameToGet),               (* data buffer *)
    udiDataSize:= SIZEOF(strHostnameToGet),      (* size of the data buffer *)
    xDone=> ,
    xBusy=> ,
    xError=> ,
    eError=> ,
    udiReceivedDataSize=> udiReceivedData );     (* if the request was successful, udiReceivedData contains the number of bytes which have been received *)
    ;
- InOut:
- Scope - Name - Type - Comment - Inherited from - Input - xExecute- BOOLRising edge: Action startsFalling edge: Resets outputsIf a falling edge occurs before the function block has completed its action, the outputs operate in the usual manner and are only reset if either the action is completed or in the event of an error. In this case, the corresponding output values (- xDone,- xError) are present at the outputs for exactly one cycle.- ETrig - Output - xDone- BOOL- TRUE: Action successfully completed- ETrig - xBusy- BOOL- TRUE: Function block active- ETrig - xError- BOOL- TRUE: Error occurred, function block aborts action- FALSE: No error- ETrig - Input - itfEtherNetIPDevice- IEtherNetIPService- BaseService - eClass- BaseService - dwInstance- DWORD- BaseService - Output - eError- BaseService - Input - wAttribute- WORD- pData- POINTER TO BYTE - udiDataSize- UDINT- Output - udiReceivedDataSize- UDINT