ReadIdentification (FB)¶
FUNCTION_BLOCK ReadIdentification EXTENDS CBM.ETrigA
Reads the identification data from a EtherCAT slave
- InOut:
- Scope - Name - Type - Initial - Comment - Inherited from - Input - xExecute- BOOLRising edge: Action startsFalling edge: Resets outputsIf a falling edge occurs before the function block has completed its action, the outputs operate in the usual manner and are only reset if either the action is completed or in the event of an error. In this case, the corresponding output values (- xDone,- xError,- iError) are present at the outputs for exactly one cycle.- ETrigA - xAbort- BOOL- TRUE: Action is stopped immediately and all outputs are reset to their initial values.- ETrigA - Output - xDone- BOOL- TRUE: Action successfully completed- ETrigA - xBusy- BOOL- TRUE: Function block active- ETrigA - xError- BOOL- TRUE: Error occurred, function block aborts action- FALSE: No error- ETrigA - xAborted- BOOL- TRUE: Action aborted by user- ETrigA - Input - usiCom- USINT- 1 - index of master 1: first Ethercat master - wSlaveIndex- WORD- index position to read identifcation from 0,1. - udiTimeOut- UDINT- Timeout for operation in ms - xReadReg0x12- BOOL- Flag if register 0x12 (station alias) should be read - xReadReg0x134- BOOL- Flag if register 0x134 (explicit device identification) should be read - xReadRegAdo- BOOL- Flag if register Ado should be read - wAdo- WORD- The address of the ado identification - Output - wStationAlias- WORD- Result for Register 0x12 - wReg134- WORD- Result for 0x134 - wAdoValue- WORD- Result für ADO identification 
