ETC_LASTERROR (ENUM)ΒΆ
TYPE ETC_LASTERROR :
- Attributes:
qualified_only- InOut:
Name
Initial
Comment
NO_ERROR
0
No error: everything running
NO_COMM
No more communication at all. More than 100 packets are not received. Perhaps cable break at the master
WRONG_WORKING_COUNTER
Working counter for processdata is wrong. One ore more slave are not operational or missing and the expected working counter is not reached
DC_TIME_ZERO
DC time from slave is always zero -> perhaps in and out connector is wrong and no time could be read from clock reference
OPEN_FIRSTADAPTER_FAILED
First Networkadapter could not be opened
OPEN_SECONDADAPTER_FAILED
Second Networkadapter could not be opened
ADAPTER_MISMATCH
Second Networkadapter usess the MAC-ID as first network adapter
NO_SLAVES_FOUND
Init slaves error: possibly slave missing or no communication at all
VENDOR_ID_WRONG
VendorID does not match
PRODUCT_ID_WRONG
ProductID does not match
NUMBER_DEVICE_MISMATCH
Read of product or vendor ID not successfull, more slaves in config as real?
SDO_WRITE_ERROR
SDO write error in startup procedure
SDO_TIMEOUT
SDO timeout in startup procedure
EMERGENCY_RECEIVED
Emergency from device received
IDN_WRITE_ERROR
IDN write error in startup procedure
IDN_TIMEOUT
IDN timeout in startup procedure
WATCHDDOG_ERROR
Watchdog expired for opmode