Master.AnalogInputGetFromPointNum (METH)¶
METHOD AnalogInputGetFromPointNum : Error
Get the value of Analog Input datapoint (DNP3 object group 30 “analog inputs”) with given point number (0 .. MaxPointNum). Returns PointNotExistent, if a datapoint with the given point number doesnt exist, OK otherwise.
- InOut:
Scope
Name
Type
Comment
Return
AnalogInputGetFromPointNumInput
pointNumberUINTPoint number.
Output
valueValue
flagsUSINT- Flags. Flag values are OR’d
- combinations of the following:
- DNPDEFS_DBAS_FLAG_ON_LINE - the point has been read
successfully
- DNPDEFS_DBAS_FLAG_RESTART - the field device that originated the
data object has been restarted. This device may be the deviced reporting this data object.
- DNPDEFS_DBAS_FLAG_COMM_LOST - the device reporting this data object
has lost communication with the originator of the data object
- DNPDEFS_DBAS_FLAG_REMOTE_FORCED - the state of the binary object
has been forced to its current state at the originating device
- DNPDEFS_DBAS_FLAG_LOCAL_FORCED - the state of the binary object
has been forced to its current state at the device reporting this data object
- DNPDEFS_DBAS_FLAG_OVER_RANGE - the digitized signal or calculation
is greater than the type specified in TMWTYPES_ANALOG_VALUE. If the SCL determines that the value returned cannot fit in the type specified by the object variation read it will set this OVER_RANGE bit.
- DNPDEFS_DBAS_FLAG_REFERENCE_CHK - the reference signal used to
digitize the signal is not stable, and the resulting digitized value may not be correct.
hasTimeStampBOOLHas a valid time stamp.
timeStampLDATE_AND_TIMETime stamp reported - valid if hasTimeStamp = TRUE, invalid otherwise.