IETrigATlTo (ITF)¶
INTERFACE IETrigATlTo EXTENDS IETrigATl, ITimeOutConstraint
In order to build a function block with an ETrigATlTo behaviour, its action provider has to be decorated with this interface.
This will determine the state machine which then forces the function block to the appropriate ETrigATlTo behaviour.
See Decorators for more information about the concept.
A state chart for function blocks with ETrigATlTo behaviour
 
- Starting
- ⇒StartActionis running, untilxCompleteisTRUE,xBusy⇒TRUEAt its beginning theSampleActionis probably executed one time.
- Executing
- ⇒ - CyclicActionis running until- xCompleteis- TRUE
- Cleaning
- ⇒CleanupActionis running. At its end theExitActionis probably executed one time.After aReady Conditionas input, only the output statesDone(xCompleteisTRUE) orError(eErrorID≠ERROR.NO_ERROR) are possible.After aError Conditionas input, only the output stateError(eErrorID≠ERROR.NO_ERROR) is possible.After aAbort Conditionas Input, only the output statesAborted(xAbortisTRUE) orError(eErrorID≠ERROR.NO_ERROR) are possible.(xBusyis stillTRUE!)
- Done
- xDone⇒- TRUE,- xBusy⇒- FALSE
- Error
- xError⇒- TRUE,- eErrorID≠- ERROR.NO_ERROR,- xBusy⇒- FALSE
- Aborted
- xAborted⇒- TRUE,- xBusy⇒- FALSE
- Resetting
- ⇒ResetActionis running, untilxCompleteisTRUE.After that:- the outputsxDone,xErrorandxAbortedwill be set toFALSE.- The outputeErrorIDwill be set toERROR.NO_ERROR.
Methods:
StartAction, inherited from IStartActionProvider