ConnectorFlags (GVL)ΒΆ
Connector flags: Flags that specifies diagnostic informations of a connector
- InOut:
Scope
Name
Type
Initial
Comment
Constant
CF_ENABLE
WORD16#1
Connector enabled
CF_DIAG_PROVIDER
WORD16#2
Connector provides diagnosis for the associated device.
CF_DEVICE_ENABLED
WORD16#4
Only valid if CF_DIAG_PROVIDER is set. Specifies if device is currently enabled (used by Reconfigure).
CF_DEMOLICENSE_ACTIVE
WORD16#8
Demo License is active
CF_DRIVER_AVAILABLE
WORD16#10
A driver is available
CF_CONNECTOR_FOUND
WORD16#20
Connector found (device detected)
CF_CONNECTOR_CONFIGURED
WORD16#40
Connector configured
CF_CONNECTOR_ACTIVE
WORD16#80
Connector active
CF_CONNECTOR_BUS_ERROR
WORD16#100
Bus error
CF_CONNECTOR_ERROR
WORD16#200
General connector error
CF_CONNECTOR_DIAGNOSTIC_AVAILABLE
WORD16#400
Diagnostic information available
CF_CONNECTOR_PASSIVE
WORD16#800
Passive mode of the second master in redundancy systems
CF_ERROR_CLEARED
WORD16#1000
An Error was automatically cleared by the driver