GeneralStatus (ENUM)¶
TYPE GeneralStatus :
- Attributes:
qualified_only- InOut:
Name
Initial
Comment
SUCCESS
0
Service was successfully performed by the object specified.
CONNECTION_FAILURE
16#1
A communications subsystem related problem was detected along the communications path.
16#2
Resources needed for the object to perform the requested service were unavailable.
INVALID_PARAM_VALUE
16#3
See Status Code 0x20, which is the preferred value to use for this condition.
PATH_SEGMENT_ERROR
16#4
The path segment identifier or the segment syntax was not understood by the processing node.
PATH_DESTINATION_UNKNOWN
16#5
The path is referencing an object class, instance or structure element that is not known or is not contained in the processing node.
PARTIAL_TRANSFER
16#6
Only part of the expected data was transferred.
SERVICE_NOT_SUPPORTED
16#8
The requested service was not implemented or was not defined for this Object Class/Instance.
INVALID_ATTRIBUTE_VALUE
16#9
Invalid attribute data detected.
ATTRIBUTE_LIST_ERROR
16#A
An attribute in the Get_Attribute_List or Set_Attribute_List response has a non-zero status.
ALREADY_IN_REQUEST_STATE
16#B
The object is already in the mode/state being requested by the service.
OBJECT_STATE_ERROR
16#C
The object cannot perform the requested service in its current mode/state.
OBJECT_ALREADY_EXISTS
16#D
The requested instance of object to be created already exists.
ATTRIBUTE_NOT_SETTABLE
16#E
A request TO modify a nonmodifiable attribute was received.
PRIVILEGE_VIOLATION
16#F
A permission/privilege check failed.
DEVICE_STATE_ERROR
16#10
The device’s current mode/state prohibits the execution of the requested service.
REPLY_DATA_TOO_LARGE
16#11
The data to be transmitted in the response is larger than the target can handle.
FRAGMENTATION_OF_VALUE
16#12
The service specified an operation that is going to fragment a primitive data value, i.e. half a REAL data type.
NOT_ENOUGH_DATA
16#13
The service did not supply enough data to perform the specified operation.
ATTRIBUTE_NOT_SUPPORTED
16#14
The attribute specified in the request is not supported.
TOO_MUCH_DATA
16#15
The service supplied more data than was expected.
OBJECT_DOES_NOT_EXIST
16#16
The object instance specified does not exist in the device.
INVALID_PARAMETER
16#20
A parameter associated with the request was invalid.
KEY_FAILURE_IN_PATH
16#25
The Key Segment that was included as the first segment in the path does not match the destination module.
PATH_SIZE_INVALID
16#26
The size of the path which was sent with the Service Request is either not large enough to allow the Request to be routed to an object or too much routing data was included.
SERVICE_NOT_SUPPORTED_FOR_SPECIFIED_PATH
16#2E
The object supports the service, but not for the designated application path (e.g. attribute).