TrendLog (FB)¶
FUNCTION_BLOCK TrendLog EXTENDS LogObjectsBase IMPLEMENTS BACnet.IBACnetEventConsumer
Default implementation to handle Trend_Log-object data storage in the file system.
Assumptions and requirements see LogObjectsBase.
TrendLog provide the feature to monitor BACnet properties, but doesnt allow to monitor other entities than BACnet properties. See ANSI/ASHRAE Standard 135-2012 Table 12-29. Properties of the Trend Log Object Type footnote [8]. Monitoring other entities (than BACnet properties) is definded in the ANSI/ASHRAE Standard 135-2012 for historic reasons and not recommended anyway. Use a BinaryInput, BinaryValue, AnalogInput or AnalogValue to represent the other entity and monitor it’s Present_Value.
TrendLog is limited to monitor properties of selected value types (BOOLEAN, UNSIGNED, SIGNED, REAL, ENUMERATED, BIT_STRING) only. To ensure the Log_DeviceObjectProperty property can not be set to other properties use the BACnet-Server-plugin LimitDeviceObjectPropertyReferencesToCertainTypes. Also TrendLog data files needs to be consistent with object persistence. Most obvious Total_Record_Count needs to be consistent with last records sequence number. So in case you delete object persistence files created by ObjectPersistence you need to delete TrendLog data files as well.
This BACnet-Server-plugin needs to be registered prior to BACnetServer.StartBACnetStack() to capture log records created during StartBACnetStack(), so you can’t use it with BACnet-Server AutoStart (at application init).
Properties:
HardShutdown, inherited from LogObjectsBase
MaxDataSize, inherited from LogObjectsBase
ObjectType, inherited from LogObjectsBase
PersistentPath, inherited from LogObjectsBase
ServerDeviceId, inherited from LogObjectsBase
TempPath, inherited from LogObjectsBase
Methods:
ComputeRecordSize, inherited from LogObjectsBase
CreateDataFiles, inherited from LogObjectsBase
DataFileName, inherited from LogObjectsBase
FreeReadRangeResult, inherited from LogObjectsBase
GetRecordsByPosition, inherited from LogObjectsBase
GetRecordsBySequence, inherited from LogObjectsBase
GetRecordsByTime, inherited from LogObjectsBase
ListDataFiles, inherited from LogObjectsBase
LogDataFile, inherited from LogObjectsBase
LogFilePos, inherited from LogObjectsBase
LogFileSize, inherited from LogObjectsBase
LogFileSizeAndPos, inherited from LogObjectsBase
LogObjectAddrString, inherited from LogObjectsBase
LogObjectPropertyAddrString, inherited from LogObjectsBase
LogReadRangeResult, inherited from LogObjectsBase
LogRecord, inherited from LogObjectsBase
LogRecordContentInfo, inherited from LogObjectsBase
ObjectId, inherited from LogObjectsBase
PostStopBACnetStack, inherited from LogObjectsBase
PurgeDataFile, inherited from LogObjectsBase
ReadNumberOfRecordsAndLastSequenceFromDataFile, inherited from LogObjectsBase
ReadNumberOfRecordsFromDataFile, inherited from LogObjectsBase
ReadRangeErrorCompletion, inherited from LogObjectsBase
ReadRangeInfoToString, inherited from LogObjectsBase
ReadRangeResultSetInfo, inherited from LogObjectsBase
RemoveDataFiles, inherited from LogObjectsBase
RemoveUnusedDataFiles, inherited from LogObjectsBase
ResetDataFile, inherited from LogObjectsBase
ScanObjectsAndSetCallbackAttachments, inherited from LogObjectsBase
SetReadCallbackAttachment, inherited from LogObjectsBase
SetWriteCallbackAttachment, inherited from LogObjectsBase
UpdateObjectPropertiesFromDataFile
WriteRecordContentToDataFile, inherited from LogObjectsBase
Structure: