Error Messages
This section contains a list of the error messages of the compiler for the CODESYS Safety for EtherCAT Safety Module extension of the CODESYS development system.
In the case of a safety application, the user can use the standard command Build (F11) of an application to manually initiate the safety-specific function for the development system part of the error checks. To do this, the safety application must be set as the active application. Before the safety application is downloaded, this process is executed automatically. At this time, error messages may appear in the standard message view, where it is possible to jump from an error code to its position in the source code.
Tip
As of SP17, the manual check is no longer performed together with F11. However, the check can be performed with the Create EtherCAT Safety Module Application command from the Build menu.
Error Number | Category | Error Text | Explanation |
|---|---|---|---|
[SELC0001] | Build | Assignment at input '{0}' not permitted | Depending on the function block type, the inputs can be linked with variables or fixed values can be specified (example: times). The direct linking of inputs with assignments is not permitted. |
[SELC0002] | Build | Function block expected | No type name is specified or an invalid type name is specified. A function block must have a valid type name. The following type names are valid:
|
[SELC0003] | Build | Identifier '{0}' already defined | The identifier has already been assigned in the project. A unique identifier must be used. |
[SELC0004] | Build | Invalid | The output of a group is linked with an invalid variable (not a safe output or a standard output). |
[SELC0005] | Build | Invalid | The input of a group is linked with an invalid variable (not a safe input or a standard input). The |
[SELC0006] | Build | Invalid | The output of a group is linked with an invalid variable (not a safe output or a standard output) or with an unknown variable. |
[SELC0007] | Build | Invalid FSoE address | The code is checked whether or not the address is a value of the data type |
[SELC0008] | Build | Invalid identifier '{0}' | The input of a function block is linked with an invalid variable (not a safe input or a standard input) or with an unknown variable. |
[SELC0009] | Build | Invalid input | The element at the input of the FB is not a box and not a variable. |
[SELC0010] | Build | Invalid input '{0}' | The value at the input has the wrong data type. |
[SELC0011] | Build | Invalid instance name '{0}' | Wrong or missing instance name. |
[SELC0012] | Build | No connections defined | At least one FSoE/TwinSAFE-SC connection must be defined in a safety application. |
[SELC0013] | Build | No function blocks defined | At least one function block must be defined in a safety application. |
[SELC0014] | Build | No groups defined | At least one group must be defined in a safety application. |
[SELC0015] | Build | No output mappings defined | At least one output mapping must be defined in a safety application. |
[SELC0016] | Warning | More than {0} bits of exchange data into the module | The maximum total length of incoming exchange data supported by the device from the standard controller is exceeded. |
[SELC0017] | Warning | More than {0} bits of exchange data from the module | The maximum total length of outgoing exchange data supported by the device to the standard controller is exceeded. |
[SELC0018] | Build | Invalid operand | The name or type of the FB main output is empty. |
[SELC0019] | Build | Invalid operand '{0}' | The name of the FB main output is not found in the process image. |
[SELC0020] | Build | Invalid OUT ERR output | The output of a group is linked with an invalid variable (not a safe output or a standard output) or with an unknown variable. |
[SELC0021] | Build | Invalid output mapping: {0} -> {1} | The mapping of a group output or the FB output (not a main output) is invalid. Local safe outputs, safe outputs, and unsafe outputs are permitted. |
[SELC0022] | Build | Invalid | The input of a group is linked with an invalid variable (not a safe input or a standard input) or with an unknown variable. |
[SELC0023] | Build | Invalid write access '{0}' | The output of a function block is linked with an invalid variable (not a safe output or a standard output) or with an unknown variable. |
[SELC0024] | Build | Instance name ‘{0}’ already exists | The instance name of a function block within a safety POU is not unique. |
[SELC0025] | Build | Input '{0}' must be used. | Specific inputs must exist. A required input must be used. |
[SELC0026] | Build | Physical device for logical device '{0}' is missing | A physical device belonging to the logical device does not exist. |
[SELC0027] | Build | Negation not permitted for input '{0}' | Specific inputs of function blocks can be normally closed or normally open contacts. Whether an input should be a normally closed contact or a normally open contact can be defined for this input in the editor by means of the Negation command. A non-negated input is a normally closed contact and a negated input is a normally open contact. If an input which can only be a normally closed contact but not a normally open contact is negated, then the error is issued. |
[SELC0028] | Build | No function blocks defined in the group | At least one function block must exist in a safety application in one of the safety POUs inserted below. |
[SELC0029] | Build | Output already mapped: {0} -> {1} | There must not be any double output linking with an safe output within a safety POU. If a safe output is used twice, then this error is issued. |
[SELC0030] | Build | Process image larger than {0} bytes | The maximum supported total length of the local process image has been exceeded. |
[SELC0031] | Build | Missing source operand | The FB output is not found in the process image. |
[SELC0032] | Build | Unknown function block ‘{0}’ | The FB type is unknown. It is possible that the library is not installed or has not been added to the Library Manager. Only FBs from |
[SELC0033] | Build | Connection: Invalid user parameters | The parameter cannot be found. Possible error in the device description. |
[SELC0034] | Build | Connection: Invalid connection parameter length | The length of the connection parameters of a safe logical exchange device is invalid. Possible error in the device description. |
[SELC0035] | Build | Connection: ‘Safe User Parameter’ must not be larger than {0} bytes | The maximum supported length of the FSoE Safe user parameters assigned to the connection has been exceeded. |
[SELC0036] | Build | Connection: Invalid user parameters | The length of the user parameters is greater than 32 bytes. Only for EL6900 |
[SELC0037] | Build | Invalid mapping |
|
[SELC0038] | Build | Invalid formal parameter | The name and type of an FB input in the internal structure is empty. |
[SELC0039] | Build | Unknown input parameter ‘{0}’ | The name of an FB input is not known because the function blocks from the |
[SELC0040] | Build | Unknown output parameter ‘{0}’ | The name of an FB output is not known because the function blocks from the |
[SELC0041] | Build | Invalid output parameter | The names and types of the FB outputs in the internal structure are wrong. |
[SELC0042] | Build | Invalid output parameter type | The type of an FB output in the internal structure is empty. |
[SELC0043] | Build | {0}: Invalid message length parameter | The parameter cannot be found or has an invalid value. Possible error in the device description. |
[SELC0044] | Build | Connection: Safety input message must not be larger than {0} bytes | The maximum supported length of the FSoE input message per connection has been exceeded. |
[SELC0045] | Build | Connection: Safety output message must not be larger than {0} bytes | The maximum supported length of the FSoE output message per connection has been exceeded. |
[SELC0047] | Build | The logical device ‘{0}’ is used in different groups (‘{1}’) | It is not allowed to use a connection in different groups. |
[SELC0048] | Build | Invalid number of input mappings | There are no input mappings or too many input mappings. For example, an input mapping is a mapped FB input. No input mappings occur if an FB is inserted but no variables are defined at the inputs or no variables are defined at the group inputs ( The maximum number of input mappings is 65535. For EK1960/EL6910 |
[SELC0049] | Build | Invalid input parameter | The names and types of the FB inputs in the internal structure are wrong. |
[SELC0050] | Build | Invalid input parameter type | The type of an FB input in the internal structure is empty. For EK1960/EL6910 |
[SELC0051] | Build | Invalid input mapping: {0} -> {1} | The assignment of a group input, FB input, or input of an FSoE/TwinSAFE-SC connection is invalid. Local safe inputs, safe inputs, and unsafe inputs are permitted. FSoE/TwinSAFE-SC connection |
[SELC0052] | Build | Input already mapped: {0} -> {1} | A group input, FB input, or input of a FSoE/TwinSAFE-SCconnection already has a mapping. |
[SELC0053] | Build | Logical exchange device ‘{0}‘ is not used in safety application and should be removed | Logical exchange devices are permitted below the EtherCAT safety application only if they are in use. If no variable from the logical exchange device is used in the FSoE safety application, then the logical exchange device must be removed. |
[SELC0054] | Build | Input ‘{0}’ is not supported by the device. | Only for EL6900 As of version 4.0.3.0 of the |
[SELC0059] | Build | Value of input ‘{0}’ is not in valid range ({1}) | |
[SELC0072] | Build | Value of ‘{0}’ does not meet the condition ‘{1}’ | For some FBs, different conditions apply to the configured values. If one of these conditions is not fulfilled, then the error is issued. For EL6910/EK1960: For EL6900: |
[SELC0081] | Build | At least two inputs of the function block must be connected. | For |
[SELC0082] | Build | This device does not support substitute values. | Only for EL6900 |
[SELC0089] | Build | More than {0} groups defined | The maximum supported total number of groups in the safety application is exceeded. |
[SELC0090] | Build | More than {0} function blocks defined | The maximum supported total number of function blocks in the safety application is exceeded. |
[SELC0091] | Build | More than {0} connections defined | The maximum supported total number of FSoE/TwinSAFE-SCconnections in the safety application is exceeded. |
[SELC0092] | Build | More than {0} connections defined in group | The maximum supported total number of FSoE connections in a group is exceeded (EL6900 only). |
[SELC0093] | Build | More than {0} output mappings defined | The maximum supported total number of output mappings in the safety application is exceeded. |
[SELC0094] | Build | Invalid number of function blocks in group | Internal error: This error only occurs with an invalid internal configuration and is normally not relevant for the user. Only for EL6900 |
[SELC0095] | Build | No connections defined in group | At least one FSoE connection must be assigned to a group. |
[SELC0103] | Build | The Standard Inputs Size of zero is not permitted. | The total length of the standard inputs must not be 0. |
[SELC0104] | Build | The function block {0} is not supported by the device. | According to the device description, the function block used is not supported by the device. |
Error Number | Category | Error Text | Explanation |
|---|---|---|---|
[SELC0055] | Build | Only one of the inputs ‘{0}’ may be set to | For For For |
[SELC0056] | Build | At least one of the inputs ‘{0}’ may be set to | For For For |
[SELC0057] | Build | At least one of the inputs '{0}' must be active | For For |
[SELC0058] | Build | Invalid output ‘{0}’. | The function block output is connected to a variable of the wrong data type (bool <-> analog). |
[SELC0060] | Build | Value of the input ‘{0}’ is not in valid range of the data type specified for ‘{1}’ | |
[SELC0061] | Build | Value of input ‘{0}’ exceeds the maximum value of the data type specified for ‘{1}’ | |
[SELC0062] | Build | Input ‘{0}’ has a {1}-bit data type, but is connected to a {2}-bit variable | An analog input configured for a 16-bit data type must not be connected to a variable of 32-bit data type and vice versa. An analog input configured for a 16-bit data type may only be connected to a variable of 16-bit data type. An analog input configured for a 32-bit data type may only be connected to a variable of 32-bit data type. |
[SELC0063] | Build | The data type of input ‘{0}’ has to be the same as the data type of the connected function block output | If an input of a function block is connected to an output of another function block, then both must be of the same data type. |
[SELC0064] | Build | Output ‘{0}’ has a {1}-bit data type, but is connected to a {2}-bit variable | An analog output configured for a 16-bit data type must not be connected to a variable of 32-bit data type and vice versa. An analog output configured for a 16-bit data type may only be connected to a variable of 16-bit data type. An analog output configured for a 32-bit data type may only be connected to a variable of 32-bit data type. |
[SELC0065] | Build | The data type of ‘{0}’ has to be the same as the data type of ‘{1} | For |
[SELC0066] | Build | The {0}-values of the ‘Value Settings’ table do not match with the selected data type of input ‘{1}’ | For |
[SELC0067] | Warning | The X-values of the ‘Value Settings’ table must be written in ascending order | For |
[SELC0068] | Warning | The Y-values of the ‘Value Settings’ table must meet the condition Y1[i] <= WY1[i] < WY2[i] <= Y2[i] | For |
[SELC0069] | Build | The Y values of the 'Value Settings' table must fulfill the condition WY1[i] <= Y1[i] < Y2[i] <= WY2[i] | For |
[SELC0070] | Build | Inputs ‘{0}’ have to be connected (operating mode ‘{1}’) | For |
[SELC0071] | Build | Input ‘{0}’ is connected, but it is not activated (operating mode ‘{1}’) | . For FB_COMPARE: The error is issued, if:
|
[SELC0073] | Build | All analog inputs and outputs must have the same data type | For |
[SELC0074] | Build | Input ‘{0}’ must not be used in pendulum mode. | For |
[SELC0075] | Build | Input ‘{0}’ must not be used in excentric mode. | For |
[SELC0076] | Build | Output '{0}' must be used in excentric mode | For |
[SELC0077] | Build | Output ‘{0}’ must be used if the input ‘{1}’ is used | For |
[SELC0078] | Build | A constant value must be set at input ‘{0}’ if the input ‘{1}’ is used. | For |
[SELC0079] | Build | Number of ‘Safe User Parameter’ configuration data pages exceeded the maximum of {0} | The maximum supported number of data pages required for the Safe User Parameters has been exceeded. |
[SELC0080] | Build | Output ‘{0}’ must be used | Specific outputs must exist. A required output must be used. |
[SELC0083] | Build | Too many substitute values in the application | The size of the data set for the substitute values has been exceeded. All substitute values of an application are stored in one data record. The maximum size of this data set is 2048 bytes. |
[SELC0084] | Build | In a passivatable group, only one connection may be defined | A POU whose properties allow passivation may only access the I/O channels of a single field device. |
[SELC0085] | Build | This group is not deactivatable. The configured substitute values are ignored. | Substitute value have been defined for signals in a POU, but deactivation is not enabled in the properties of this POU. |
[SELC0086] | Build | A substitute value for an output must not be defined more than one time. | Several substitute values are defined for one output in a safety POU. However, only one substitute value is permitted. |
[SELC0087] | Build | Substitute value does not match the data type of the output '{0}' | The data type of the replacement value must be compatible with the data type of the output. |
[SELC0096] | Build | More than {0} TwinSAFE-SC Master connections | The maximum number of TwinSAFE-SC Master connections supported by the device has been exceeded. |
[SELC0097] | Build | Near process image size exceeds the maximum of {0} bytes | The maximum total length of the near-process image (process image without FB status data) supported by the device has been exceeded. |
[SELC0098] | Build | EtherCAT input size exceeds the maximum of {0} bytes | The maximum total length of standard inputs and FSoE input messages supported by the device has been exceeded. During the check, an additional 1 byte each is taken into account for the |
[SELC0099] | Build | EtherCAT output size exceeds the maximum of {0} bytes | The maximum total length of standard outputs and FSoEoutput messages supported by the device has been exceeded. During the check, an additional 1 byte each is taken into account for the |
[SELC0100] | Build | Cyclic FRAM data size exceeds the maximum of {0} bytes | The maximum length supported by the device in FRAM for customizing has been exceeded. |
[SELC0101] | Build | Number of | The maximum supported number of |
[SELC0102] | Build | Mapping code size has exceeded the maximum of {0} bytes | The maximum supported size of the code generated for the mappings in the device has been exceeded. |