Error Messages
Error Number | Message | Typical Error Cause | Correction |
|---|---|---|---|
8448 | Identity mismatch | The application information on the target device and the HMI to not match. | Download to the HMI again in order to update the application information. |
8449 | Login failed |
| Check the communication settings for the target device. Make sure that the user name and password are correct. |
8450 | Login necessary | There is no connection to the controller. | Check the communication settings for the target device. Make sure that the user name and password are correct. |
8451 | The driver is currently busy executing a different request. | Too many requests (subscriptions) are being processed per cycle. As a result, the driver needs more time to process the data. | Reduce the base load, for example by adjusting the |
8452 | The device cannot be reached. |
| Make sure that the target device is switched on. Check the communication settings and the network connection to the target device. |
8453 | The device name is not unique. | Multiple devices with the same name were found in the target system. | Make sure that the target device has a unique name. |
8454 | No symbols available | Either no application has been downloaded to the target device, or an application with another symbol configuration. | Make sure that the application is downloaded with the correct symbol configuration to the target device. |
8457 | The connection is denied due to no resources. | All available communication channels of the target device are used. |