SMC_SmoothBSpline (FB)¶
FUNCTION_BLOCK FINAL SMC_SmoothBSpline
Smoothes segments of consecutive G1 elements with a B-Spline of fifth degree. Each segment of at least 5 consecutive G1 elements of non-zero length is replaced by splines. The start and end positions of the G1 elements serve as control points of the B-spline that is created. Only the start position of the segment and the end position are interpolated exactly.
Each segment of n >= 5 G1 elements is replaced by n-5 polynomials.
Note
Does not support H-functions
Does not support changes of flags like G51, G52, G40 and so on, these changes are ignored
Requires 3D-Mode
Can be turned on and off from G-Code using G38/G39
A spline always contains the same tool correction information (i.e. lengths and diameter) as the first of the segments that it replaces.
Elements other than G1 (e.g. G0, G2, G3, …) interrupt the smoothing until the next G1 element.
Probe movements / G31 are not supported.
Additional axis: First the values of the additional axis are also converted to a B-spline. For the linear axis (P,Q,U,V,W) only the positions at the end of each polynomial are stored in SMC_GeoInfo. For the smoothed axis (A, B, C) the slope is also stored.
- InOut:
Scope
Name
Type
Comment
Input
bExecuteBOOLExecution starts on the rising edge.
poqDataInPOINTER TO SMC_OUTQUEUE
Input path queue
nSizeOutQueueUDINTSize of the data buffer
pbyBufferOutQueuein bytes.pbyBufferOutQueuePOINTER TO ARRAY [0..0] OF SMC_GEOINFO
Points to the first byte of the memory area being allocated for the SMC_OUTQUEUE-structure. This area must be at least as big as defined in
nSizeOutQueue. Typically the allocation of the memory buffer is done within the declaration part of the IEC-program by defining an array of SMC_GeoInfo (ExampleBuf:ARRAY[1..50] OF SMC_GEOINFOfor a buffer which can hold 50 path` elements). After predefining the value it may be modified during a reset only.eModeThe element type applied for the smoothing of the axes.
wFeatureFlagWORDThe feature bit (0..31) used for smoothing (controlled by G38/G39)
Output
bDoneBOOLWill be set to
TRUEas soon as the input data frompoqDataInhas been processed completely. Afterwards, the function block will not perform any further actions until it gets reset. If thebExecuteinput isFALSE, bDone will be reset toFALSE.bBusyBOOLTRUE, while execution of function block is not finished.bErrorBOOLSignals, that an error has occurred within the function block.
wErrorIDSMC_ERRORError identification.
poqDataOutPOINTER TO SMC_OUTQUEUE
The queue for the output path
Structure: